| 2022-05-09 17:27:16 | PLAN REVIEW COMMENTS FOR THIS REVISION |
| | |
| | 1ST REVIEW: THIS PROJECT IS PERMITTED UNDER THE FBC |
| | FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) ON SHEET A1.108 CHANGES WERE MADE TO THE MEN AND |
| | WOMEN GROUP BATHROOMS AND THEY ARE NOT CLOUDED. FBC |
| | 107.2.1 |
| | |
| | 2) ALSO ON SHEET A1.108 THE DOORS FROM THE TENNIS |
| | COURTS (0833) TO THE CIRCULATION AREA (0854) HAVE BEEN |
| | ELIMINATED BUT ARE NOT CLOUDED. THIS EFFECTS EGRESS |
| | FROM THE TENNIS COURT AREA. SUBMIT A NEW LIFE SAFETY |
| | PLAN FOR THIS AREA WITH OCCUPANT LOADS, EXIT |
| | SEPARATION, ETC. FBC CHAPTER 10 AND 107.3.5.1.1 |
| | |
| | 3) ON SHEET A1.112 THERE ARE NO LAVATORIES SHOWN IN THE |
| | BATHROOMS FOR UNIT D1 - R1204. FBC 107.2.1 |
| | |
| | 4) ON SHEET A1.265 THERE IS A BATHTUB SHOWN INSIDE ONE |
| | OF THE BEDROOMS OF UNIT B2 - R1303. FBC 107.2.1 |
| | |
| | 5) THE FLOOR PLANS FOR LEVELS 17, 18 AND 19 A1.269 AND |
| | A1.269A SHOW THE DOOR FROM THE FIRE LOBBY TO STAIR #2 |
| | HAS BEEN ELIMINATED. FBC 3007.6.1 REQUIRES DIRECT |
| | ACCESS FROM THE FIRE ACCESS LOBBY TO THE INTERIOR EXIT |
| | STAIRWAY. |
| | |
| | 6) THE USABLE BATHROOMS HAVE NOT BEEN IDENTIFIED AS |
| | SPECIFICATION A OR B AS SPECIFIED BY FAIR HOUSING |
| | GUIDELINES FOR SOME OF THE ENLARGED UNIT PLANS. FAIR |
| | HOUSING GUIDELINES REQUIREMENT 7(2) |
| | |
| | 7) THE REQUIRED CLEAR FLOOR SPACE FOR THE BATHROOMS HAS |
| | NOT BEEN INDICATED ON SOME OF THE ENLARGED UNIT PLANS. |
| | FOR EXAMPLE UNIT B 4.3 ON SHEET A1.512 DOES NOT APPEAR |
| | TO HAVE THE REQUIRED CLEAR FLOOR SPACE OF 30" X 48" |
| | OUTSIDE OF THE DOOR SWING. FAIR HOUSING GUIDELINES |
| | REQUIREMENT 7(2) PLEASE CORRECT. |
| | |
| | 8) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |