Plan Review Notes
Plan Review Notes For Permit 22020810
Permit Number 22020810
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-02-18 11:44:54FIRE PROVISO COMMENTS:
 CLASS K PORTABLE EXTINGUISHER LOCATED WITHIN 30 FT. OF
 COOKING SURFACES, WITH MOUNTING HEIGHT AT LEAST 4
 INCHES OFF THE GROUND UP TO A MAXIMUM OF 5FT TO THE TOP
 OF THE EXTINGUISHER.
 IF THE BUILDING IS EQUIPPED WITH A FIRE ALARM SYSTEM,
 THE ACTIVATION OF THE HOOD SYSTEM SHALL ACTIVATE A
 GENERAL FIRE ALARM. CONNECTION TO THE BUILDING FIRE
 ALARM SYSTEM SHALL BE PERFORMED BY CONTRACTOR PROPERLY
 LICENSED TO WORK/INSTALL FIRE ALARM SYSTEMS.
  