| 2023-07-13 12:04:20 | 3RD REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22070746 |
| | 7/13/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | FAILED COMMENT #11 FROM FROM THE 1ST AND 2ND REVIEW, |
| | AND FAILED COMMENTS #1 & 2 FROM THE 2ND REVIEW ARE |
| | LISTED BELOW WITH ADDITIONAL NOTES. |
| | |
| | 11) FAILED- NOT PROVIDED. A2.2: PROVIDE THE DIMENSIONS |
| | OF THE STANDARD (NON-ADA) WATER CLOSET COMPARTMENTS- |
| | SEC. 405.3.1 FBC P. |
| | SHEETS A2-2 & A2-2B: THE TYPICAL NON-ADA WATER CLOSET |
| | COMPARTMENT DETAIL SHOWS 4'3" (51-INCHES) DEPTH |
| | MEASUREMENT HOWEVER SEC. 405.3.1 FBC P REQUIRES |
| | 56-INCHES FOR WALL-HUNG WATER CLOSETS. PLEASE REVISE |
| | THE DETAIL AND THE COMPARTMENTS SHOWN ON THE WEST SIDE |
| | OF THE WOMEN'S RESTROOM- DETAIL 1/A2.2. PLEASE NOTE THE |
| | NEW PLUMBING FIXTURE SCHEDULE IS CALLING OUT A SLOAN |
| | ST-2029-A WATER CLOSETS WHICH ARE FLOOR MOUNTED. |
| | COMPARTMENT DEPTH INCREASES TO 60-INCHES FOR FLOOR |
| | MOUNTED. |
| | |
| | 1) SHEET A2.2-B PRIVATE RESTROOMS: THE EXCEPTIONS IN |
| | THE FBC ACC FOR PRIVATE RESTROOM PLUMBING FIXTURE ADA |
| | COMPLIANCE INDICATE PRIVATE RESTROOMS ARE THOSE THAT |
| | ARE ACCESSED THROUGH A PRIVATE OFFICE. PRIVATE |
| | RESTROOMS #1 & 2 ARE NOT ACCESSED THROUGH A PRIVATE |
| | OFFICE. PLEASE REFER TO SECS. 604.4 (SEAT HEIGHT), |
| | 604.5 (WC GRAB BARS), 606.2 (LAVATORY CLEAR FLOOR |
| | SPACES AND KNEE AND TOE CLEARANCES,), 606.3 (LAV |
| | HEIGHT), 608.3 (SHOWER GRAB BARS). THE ARCHITECT CAN |
| | USE SEC. 213.2 EXCEPTION 4 FOR MULTIPLE SINGLE USER |
| | TOILETS ROOMS IN A CLUSTER WHICH WOULD ALLOW NO MORE |
| | THAN 50 PERCENT OF THE TOILET ROOMS TO BE MEET ADA |
| | COMPLIANCE. FULL COMPLIANCE FOR THE SHOWER HOWEVER IS |
| | REQUIRED PER SEC. 213.3.6. |
| | PLEASE PROVIDE THE FOLLOWING DETAILS PER THE FBC ACC. |
| | ALTERNATIVELY THE ARCHITECT CAN REFERENCE SOME OF THE |
| | COMPLIANCE DETAILS SHOWN ON SHEET A2.2-A. |
| | |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORIES- SECTION 606.2. PLEASE NOTE THAT THE DOOR IN |
| | PRIVATE RESTROOM #1 APPEARS TO BE SWINGING INTO THE |
| | CLEAR FLOOR SPACE OF THE LAVATORY WHICH IS NOT ALLOWED |
| | PER SEC. 603.2.3. |
| | C) TURNING SPACE DIAMETERS- SECTION 304.3. |
| | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| | WALLS- SECTION 604.2. |
| | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | F) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER |
| | SURFACES FROM THE FINISHED FLOOR- SECTION 606.3. |
| | G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SECTION 603.3 |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604. |
| | I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS - |
| | SECTION 604.6. |
| | J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2. |
| | |
| | 2) A2.2-B: SHOWER-PLEASE NOTE THE DETAILS ON A2.2-A FOR |
| | THE ALTERNATE TYPE ROLL-IN SHOWER DO NOT MATCH WITH THE |
| | NEW STANDARD ROLL-IN SHOWER. |
| | |
| | L) SHOW THE REQUIRED 30 INCH WIDE MINIMUM BY 60 INCH |
| | LONG MINIMUM CLEARANCE SHALL BE PROVIDED ADJACENT TO |
| | THE OPEN FACE OF THE SHOWER COMPARTMENT. |
| | M) SHOW LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF |
| | GRAB BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND |
| | 608.3.2. |
| | N) SHOW THE LOCATION OF CONTROL, FAUCET, AND SHOWER |
| | SPRAY IN THE SHOWER- SECTION 608.5.2. |
| | O) PROVIDE SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION |
| | 608.6. |
| | P) SHOW THE THRESHOLD FOR THE NEW ROLL-IN SHOWER SHALL |
| | BE 1/2-INCH HIGH MAXIMUM- SEC. 608.7 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |