Plan Review Notes
Plan Review Notes For Permit 22020746
Permit Number 22020746
Review Stop P
Sequence Number 3
Notes
Date Text
2023-07-13 12:04:203RD REVIEW FBC-2020 PLUMBING
 PERMIT- 22070746
 7/13/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 FAILED COMMENT #11 FROM FROM THE 1ST AND 2ND REVIEW,
 AND FAILED COMMENTS #1 & 2 FROM THE 2ND REVIEW ARE
 LISTED BELOW WITH ADDITIONAL NOTES.
  
 11) FAILED- NOT PROVIDED. A2.2: PROVIDE THE DIMENSIONS
 OF THE STANDARD (NON-ADA) WATER CLOSET COMPARTMENTS-
 SEC. 405.3.1 FBC P.
 SHEETS A2-2 & A2-2B: THE TYPICAL NON-ADA WATER CLOSET
 COMPARTMENT DETAIL SHOWS 4'3" (51-INCHES) DEPTH
 MEASUREMENT HOWEVER SEC. 405.3.1 FBC P REQUIRES
 56-INCHES FOR WALL-HUNG WATER CLOSETS. PLEASE REVISE
 THE DETAIL AND THE COMPARTMENTS SHOWN ON THE WEST SIDE
 OF THE WOMEN'S RESTROOM- DETAIL 1/A2.2. PLEASE NOTE THE
 NEW PLUMBING FIXTURE SCHEDULE IS CALLING OUT A SLOAN
 ST-2029-A WATER CLOSETS WHICH ARE FLOOR MOUNTED.
 COMPARTMENT DEPTH INCREASES TO 60-INCHES FOR FLOOR
 MOUNTED.
  
 1) SHEET A2.2-B PRIVATE RESTROOMS: THE EXCEPTIONS IN
 THE FBC ACC FOR PRIVATE RESTROOM PLUMBING FIXTURE ADA
 COMPLIANCE INDICATE PRIVATE RESTROOMS ARE THOSE THAT
 ARE ACCESSED THROUGH A PRIVATE OFFICE. PRIVATE
 RESTROOMS #1 & 2 ARE NOT ACCESSED THROUGH A PRIVATE
 OFFICE. PLEASE REFER TO SECS. 604.4 (SEAT HEIGHT),
 604.5 (WC GRAB BARS), 606.2 (LAVATORY CLEAR FLOOR
 SPACES AND KNEE AND TOE CLEARANCES,), 606.3 (LAV
 HEIGHT), 608.3 (SHOWER GRAB BARS). THE ARCHITECT CAN
 USE SEC. 213.2 EXCEPTION 4 FOR MULTIPLE SINGLE USER
 TOILETS ROOMS IN A CLUSTER WHICH WOULD ALLOW NO MORE
 THAN 50 PERCENT OF THE TOILET ROOMS TO BE MEET ADA
 COMPLIANCE. FULL COMPLIANCE FOR THE SHOWER HOWEVER IS
 REQUIRED PER SEC. 213.3.6.
 PLEASE PROVIDE THE FOLLOWING DETAILS PER THE FBC ACC.
 ALTERNATIVELY THE ARCHITECT CAN REFERENCE SOME OF THE
 COMPLIANCE DETAILS SHOWN ON SHEET A2.2-A.
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2. PLEASE NOTE THAT THE DOOR IN
 PRIVATE RESTROOM #1 APPEARS TO BE SWINGING INTO THE
 CLEAR FLOOR SPACE OF THE LAVATORY WHICH IS NOT ALLOWED
 PER SEC. 603.2.3.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOOR- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 2) A2.2-B: SHOWER-PLEASE NOTE THE DETAILS ON A2.2-A FOR
 THE ALTERNATE TYPE ROLL-IN SHOWER DO NOT MATCH WITH THE
 NEW STANDARD ROLL-IN SHOWER.
  
 L) SHOW THE REQUIRED 30 INCH WIDE MINIMUM BY 60 INCH
 LONG MINIMUM CLEARANCE SHALL BE PROVIDED ADJACENT TO
 THE OPEN FACE OF THE SHOWER COMPARTMENT.
 M) SHOW LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND
 608.3.2.
 N) SHOW THE LOCATION OF CONTROL, FAUCET, AND SHOWER
 SPRAY IN THE SHOWER- SECTION 608.5.2.
 O) PROVIDE SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION
 608.6.
 P) SHOW THE THRESHOLD FOR THE NEW ROLL-IN SHOWER SHALL
 BE 1/2-INCH HIGH MAXIMUM- SEC. 608.7
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  