| 2023-07-17 14:40:43 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22020746 |
| | ADD: 2951 ELECTRONICS WAY |
| | CONT: SURFSIDE CONTRACTING/ CGC |
| | TEL: 561-748-6022 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: JULY 17TH/2023 |
| | ACTION: DENIED |
| | |
| | 1) 3RD REQUEST, TO DATE THIS PERMIT HAS NOT BEEN |
| | RESUBMITTED. PERMIT 21111052(EXPIRED) 2951 ELECTRONIC |
| | WAY INSTALL EGRESS DOORS, RAMP, LANDING AND STAIRS NOT |
| | PERMITTED. ON 6/6/2022 APPLICANT NEEDS TO RESUBMIT. |
| | 4XFEE ADDED TO PERMIT. GOOGLE EARTH SHOWS WORK |
| | COMPLETE. THIS WORK HAS TO BE ACCOUNTED FOR BEFORE THIS |
| | PERMIT CAN BE ISSUED. THE OWNER OF THE PROPERTY HAS TO |
| | TAKE RESPONSIBILITY FOR ALL UNPERMITTED WORK, EVEN IF |
| | IT WAS COMPLETED UNDER A PREVIOUS OWNER. CONFORMANCE. |
| | 2020 EXISTING BUILDING CODE, LEVEL-1 ALTERATION 701.2, |
| | LEVEL-2 ALTERATION 801.3, & LEVEL-3 ALTERATIONS |
| | 901.2COMPLIANCE. AN EXISTING BUILDING OR PORTION |
| | THEREOF SHALL NOT BE ALTERED SUCH THAT THE BUILDING |
| | BECOMES LESS SAFE THAN ITS EXISTING CONDITION. |
| | |
| | 2) 3RD REQUEST. NEW PLATFORM STAGE. THE RESPONSE LETTER |
| | STATES SEE SHEET A2.0D NO SUCH SHEET IN THE PLAN SET |
| | NOR IN THE INDEX. THE OTHER SHEET MENTIONED FOR THE |
| | STAGE IS A2-0, THERE IS NO INFORMATION ON THIS SHEET, |
| | CUT SECTION OR DETAILS AS TO THE STAGE CONSTRUCTION |
| | COMPLIANCE WITH WILL NEED TO COMPLY WITH THE 2020 |
| | FBC-BUILDING SECTION 410, STAGES, PLATFORMS AND |
| | TECHNICAL PRODUCTION AREAS, PROSCENIUM WALL AND OR |
| | CURTAINS, ROOF VENTS SMOKE CONTROL, ETC. SHEET A4.0 |
| | NOTE 6 STATES THE EXISTING STAGE IS COMPRISED OF 2 INCH |
| | PLYWOOD, METAL FRAMING. PLEASE REVIEW SECTION 410.3.1. |
| | EXCEPTION 1, 2-INCH-THICK WOOD DECK OR 410.4 FIRE- |
| | RETARDANT- TREATED WOOD. PLEASE PROVIDE THE LOAD |
| | BEARING COMPACITY OF STAGE IN COMPLIANCE WITH 2020 |
| | FBC-BUILDING TABLE 1607.1. THE STAGE WILL ALSO NEED TO |
| | SHOW COMPLIANCE WITH 410.3.7 OF THE 2020 FBC-BUILDING |
| | CODE. |
| | 2ND REQUEST, STAGE, IT DOES NOT MATTER, IT IS |
| | NON-PERMITTED WORK THERE FOR CONSIDERED NEW WORK. AGAIN |
| | BEFORE THIS PERMIT CAN BE ISSUED, THE STAGE HAS TO MEET |
| | ALL CODE REQUIREMENTS FOR NON-PERMITTED WORK. PERMIT |
| | 22020746 SHEET A2-0 OVERALL FLOOR PLAN- LIFE SAFETY. |
| | NOTE THAT THE EXISTING STAGE AREA TO REMAIN AT +30 |
| | INCHES AFF. PLEASE NOTE THERE WAS NEVER A PERMIT PULLED |
| | FOR THE BUILDING OF THE STAGE OR ANY AREAS BUILT AT 30 |
| | INCHES AFF. THESE AREAS WILL BE TREATED AS NEW |
| | CONSTRUCTION. 2020 EXISTING BUILDING CODE. 801.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. WILL NEED TO |
| | COMPLY WITH THE 2020 FBC-BUILDING SECTION 410, STAGES, |
| | PLATFORMS AND TECHNICAL PRODUCTION AREAS, PROSCENIUM |
| | WALL AND OR CURTAINS, ROOF VENTS SMOKE CONTROL, ETC. |
| | SHEET A4.0 NOTE 6 STATES THE EXISTING STAGE IS |
| | COMPRISED OF ?? INCH PLYWOOD, METAL FRAMING. PLEASE |
| | REVIEW SECTION 410.3.1. EXCEPTION 1, 2-INCH-THICK WOOD |
| | DECK OR 410.4 FIRE- RETARDANT- TREATED WOOD. PLEASE |
| | PROVIDE THE LOAD BEARING COMPACITY OF STAGE IN |
| | COMPLIANCE WITH 2020 FBC-BUILDING TABLE 1607.1. |
| | THE STAGE WILL ALSO NEED TO SHOW COMPLIANCE WITH |
| | 410.3.7 OF THE 2020 FBC-BUILDING CODE. |
| | 2A) 2ND REQUEST. COVERSHEET UNDER THE PROJECT DATA LIST |
| | THE CLASSIFICATION OF WORK AS ALTERATION LEVEL 2/ |
| | EXPANSION. THE PROJECT NEEDS TO BE REVIEWED UNDER THE |
| | 2020 EXISTING BUILDING CODE FOR CHANGE IN OCCUPANCY |
| | CHAPTER 10, FOR THE LATERAL ADDITION CHAPTER 11 AND THE |
| | 2020 FBC-BUILDING CODE FOR NEW NON-PERMITTED WORK. THE |
| | BOTTOM LEFT CORNER STILL STATES LEVEL II ALTERATION. |
| | |
| | 3A) COMPLIED. |
| | |
| | 3B) 3RD REQUEST. THE ISSUE IS NOT THAT SHEET A-100 IS |
| | NO LONGER APPLICABLE, THE STATEMENT THE VIP MODULAR |
| | BUILDINGS AND 8 TRAILERS HAVE BEEN REMOVED FROM THE |
| | PLANS, THE ISSUE IS, ARE THESE UNITS STILL AT THE SITE |
| | AND PART OF THE UNPERMITTED WORK. CONFORMANCE. 2020 |
| | EXISTING BUILDING CODE, LEVEL-1 ALTERATION 701.2, |
| | LEVEL-2 ALTERATION 801.3, & LEVEL-3 ALTERATIONS |
| | 901.2COMPLIANCE. AN EXISTING BUILDING OR PORTION |
| | THEREOF SHALL NOT BE ALTERED SUCH THAT THE BUILDING |
| | BECOMES LESS SAFE THAN ITS EXISTING CONDITION. |
| | 1ST ROUND OF COMMENTS. THE SITE PLAN & LIFE SAFETY PLAN |
| | SHOWS THE VIP MODULAR BUILDING AND 8 TRAILERS ON SITE, |
| | MANY OF THESE ARE ALSO MODULAR BUILDINGS THAT HAVE NOT |
| | APPLIED FOR PERMITS, WHY HAS NO PERMIT BEEN APPLIED |
| | FOR? 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 105.1 PERMITS. |
| | |
| | 3C-N) COMPLIED. |
| | |
| | |
| | 4) COMPLIED. |
| | |
| | 5A-F) COMPLIED. |
| | |
| | 6) COMPLIED. |
| | 7-8) COMPLIED, NEW DESIGN |
| | |
| | 9) 3RD REQUEST. SHEET A2.2 NEW GANGED RESTROOMS: |
| | 9A) WOMENS/MENS/ STAFF RESTROOM, THE INSIDE DIMENSION |
| | IS 7 FEET 1 INCH, THE BACK WALL WHERE THE WATER CLOSET |
| | AND LAV ARE LOCATED SHOULD BE 7 FEET ONE INCH. IN ALL |
| | RESTROOMS THE CLEAR FLOOR SPACE THE 60 INCHES IS TAKEN |
| | ON THE BACK WALL FROM THE SIDE WALL CLOSET TO THE WATER |
| | CLOSET TO THE LAV WITH THE WATER CLOSET AT 18 INCHES |
| | CENTERLINE FROM SIDE WALL AND LAV IS ALSO CENTERLINE AT |
| | 18 INCHES FROM SIDE WALL THIS DIMENSION WILL NOT |
| | PROVIDE THE 60 INCHES REQUIRED FOR CLEAR FLOOR SPACE |
| | FOR THE WATER CLOSET. CLEARANCES AT WATER CLOSETS. |
| | 604.3 CLEARANCE. CLEARANCES AROUND THE WATER CLOSETS |
| | AND IN TOILET COMPARTMENTS SHALL COMPLY WITH 604.3. |
| | 604.3.1. SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE |
| | 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES MINIMUM PERPENDICULAR FROM THE REAR |
| | WALL. PLANS SHOW THE DIMENSIONS BACKWARDS. NOTE THE |
| | MINIMUM BACK WALL MEASUREMENT SHOULD BE 7-FOOT 1 INCH |
| | (FINISHES MAY ENCROACH) ON THE FINISH DIMENSION WITH |
| | LAV AT CENTERLINE 15 INCHES!!! |
| | |
| | |
| | 10-12) COMPLIED. |
| | |
| | 13) SEMI-COMPLIED, SUBMITTED. SHEETS A3-0 & A3-1 |
| | ELEVATIONS. COMPONENTS & CLADDING. PLEASE SUBMIT THE |
| | COMPONENTS AND CLADDING PRODUCT APPROVALS. 2020 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS:(31)(C) ROOFING PRODUCTS AND ASSEMBLIES, |
| | |
| | 14) ARCHITECT APPROVAL, APPROVED, WITH EXCEPTION NO |
| | ROOFING PRODUCT APPROVAL WAS SUBMITTED. |
| | |
| | 15) / ACKNOWLEDGED DELEGATED ENGINEERING. 61G15-30. |
| | |
| | 16)2ND REQUEST. ROOFING:NO PRODUCT APPROVAL WAS |
| | SUBMITTED FOR ROOFING. 220 FOR ALL ROOFING PRODUCTS |
| | PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR |
| | ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW THE |
| | PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS |
| | ALLOWED FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL |
| | BE INCREASED FOR BOTH INSULATION & THE BASE SHEET AS |
| | CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION |
| | STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |
| | 17) COMPLIED/ ACKNOWLEDGED. |
| | |
| | 18) 2ND REQUEST. THE STRUCTURAL SHEETS SHOW NEW |
| | STRUCTURAL ELEMENTS, THIS WILL CREATE THE PROJECT TO BE |
| | A THRESHOLD BUILDING. THRESHOLD BUILDING / FL S. S. |
| | 553.71(7) THRESHOLD BUILDING" MEANING ANY BUILDING |
| | WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, |
| | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS |
| | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 |
| | SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN |
| | 500 PERSONS. |
| | |
| | 18A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN. |
| | |
| | 18B) SEMI-COMPLIED. PAGE 6 WAS SUBMITTED, MISSING PAGES |
| | 7 SITE INSPECTOR, PAGE 8 CONTRACTOR & OWNER SIGNATURES. |
| | THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT |
| | BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO |
| | THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT |
| | ISSUANCE WILL TAKE PLACE. PLEASE REVIEW THE GUIDELINES |
| | AND POLICIES FOR PROJECTS CONCERNING THRESHOLD |
| | INSPECTOR PAGES 1-5, PAGES 6-8 THRESHOLD INSPECTOR |
| | FORMS. |
| | E-MAIL SENT WITH ATTACHMENT TO: : |
| | [email protected] 12/28/2022 8:34 AM. |
| | |
| | 18C) 3RD REQUEST. PLEASE PROVIDE WHAT PLAN SHEET I CAN |
| | FIND THE REQUIRED STATEMENT, THANK YOU. THRESHOLD |
| | BLDG., REQUIRED STATEMENT: W.P.B. AMENDMENT 110.3.7.4.4 |
| | ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE |
| | SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE FIRE-SAFETY |
| | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| | |
| | 18D) COMPLIED. SPECIAL INSPECTOR PLEASE PROVIDE A |
| | RESUME'. |
| | |
| | 18E-F ) ACKNOWLEDGED, |
| | |
| | 19) COMPLIED. SHEET S0.3 COMPONENTS & CLADDING |
| | ALLOWABLE PRESSURES. |
| | |
| | 20) COMPLIED. TYPE IIB. |
| | |
| | 21) COMPLIED. |
| | |
| | 22) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |