2023-05-15 14:20:43FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-702
  
 1) GENERATOR REQUIRES SEPARATE PLANS AND PERMIT. SHOW
 LOCATION OF GENERATOR ON PLANS.
  
 2) FAULT CURRENT CALCULATION ON SERVICE REQUIRED
 110.10, 110.9
  
 3) PLANS AND PERMIT WILL BE REQUIRED FOR OWNER
 INSTALLED EQUIPMENT, AUDIO, IT, VIDEO, LIGHTING RACKS.
  
 4) SERVICE #2 MAIN NEEDS TO BE IDENTIFIED AS ONE OF TWO
 AND SO FORTH.
 230.2(E) IDENTIFICATION. WHERE A BUILDING OR STRUCTURE
 IS SUPPLIED BY MORE THAN ONE SERVICE, OR ANY
 COMBINATION OF BRANCH CIRCUITS, FEEDERS, AND SERVICES,
 A PERMANENT PLAQUE OR DIRECTORY SHALL BE INSTALLED AT
 EACH SERVICE DISCONNECT LOCATION DENOTING ALL OTHER
 SERVICES, FEEDERS, AND BRANCH CIRCUITS SUPPLYING THAT
 BUILDING OR STRUCTURE AND THE AREA SERVED BY EACH. SEE
 225.37.
 PLEASE SHOW LOCATION OF ALL SERVICES INTO THE BUILDING.
 230.2
  
 PAGES EL201,202,203,204
  
 5) SITCHES HAVE THE DESINATION OF TS, M, TM3, S3, S4
 NOT ON YOUR SCHEDULE PAGE
  
 PAGES EP 201,202, 204, 205, 206
  
 6) OUTLETS INSIDE AND OUTSIDE HAVE SAME DESIGNATION OF
 WP/G ?
  
 7) OUTLETS REQUIRED AT UPS LOCATION AAND TRANSFORMER
 LOCATIONS FOR SERVICING, 210.64
  
 PAGE E605
  
 8) MTS NOT SHOWN ON RISER?
  
 PAGE FA 000
  
 9) SEPARATE PLANS AND PERMIT REQUIRED
  
 10) NO PAGE NUMBER VALUE OF JOB SEEMS LOW FOR THE
 AMOUNT OF WORK TO BE PERFORMED, PLEASE SUBMIT A COST
 BREAK DOWN OF ALL CONTRACTOR AND CUSTOMER SUPLLIED
 EQUIPMENT AND LABOR. (3.75M)
  
 11) PAGE E-702 NOTE 8 MISSING