2023-06-01 11:55:15WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22020746
 ADD: 2951 ELECTRONICS WAY
 CONT: SURFSIDE CONTRACTING/ CGC
 TEL: 561-748-6022
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: JUNE 06TH/2023
 ACTION: DENIED
  
 1) 2ND REQUEST, TO DATE THIS PERMIT HAS NOT BEEN
 RESUBMITTED. PERMIT 21111052(EXPIRED) 2951 ELECTRONIC
 WAY INSTALL EGRESS DOORS, RAMP, LANDING AND STAIRS NOT
 PERMITTED. ON 6/6/2022 APPLICANT NEEDS TO RESUBMIT.
 4XFEE ADDED TO PERMIT. GOOGLE EARTH SHOWS WORK
 COMPLETE. THIS WORK HAS TO BE ACCOUNTED FOR BEFORE THIS
 PERMIT CAN BE ISSUED.
  
 2) 2ND REQUEST, STAGE, IT DOES NOT MATTER, IT IS
 NON-PERMITTED WORK THERE FOR CONSIDERED NEW WORK. AGAIN
 BEFORE THIS PERMIT CAN BE ISSUED, THE STAGE HAS TO MEET
 ALL CODE REQUIREMENTS FOR NON-PERMITTED WORK. PERMIT
 22020746 SHEET A2-0 OVERALL FLOOR PLAN- LIFE SAFETY.
 NOTE THAT THE EXISTING STAGE AREA TO REMAIN AT +30
 INCHES AFF. PLEASE NOTE THERE WAS NEVER A PERMIT PULLED
 FOR THE BUILDING OF THE STAGE OR ANY AREAS BUILT AT 30
 INCHES AFF. THESE AREAS WILL BE TREATED AS NEW
 CONSTRUCTION. 2020 EXISTING BUILDING CODE. 801.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING. WILL NEED TO
 COMPLY WITH THE 2020 FBC-BUILDING SECTION 410, STAGES,
 PLATFORMS AND TECHNICAL PRODUCTION AREAS, PROSCENIUM
 WALL AND OR CURTAINS, ROOF VENTS SMOKE CONTROL, ETC.
 SHEET A4.0 NOTE 6 STATES THE EXISTING STAGE IS
 COMPRISED OF ?? INCH PLYWOOD, METAL FRAMING. PLEASE
 REVIEW SECTION 410.3.1. EXCEPTION 1, 2-INCH-THICK WOOD
 DECK OR 410.4 FIRE- RETARDANT- TREATED WOOD. PLEASE
 PROVIDE THE LOAD BEARING COMPACITY OF STAGE IN
 COMPLIANCE WITH 2020 FBC-BUILDING TABLE 1607.1.
 THE STAGE WILL ALSO NEED TO SHOW COMPLIANCE WITH
 410.3.7 OF THE 2020 FBC-BUILDING CODE.
 2A) NEW COMMENT. COVERSHEET UNDER THE PROJECT DATA LIST
 THE CLASSIFICATION OF WORK AS ALTERATION LEVEL 2/
 EXPANSION. THE PROJECT NEEDS TO BE REVIEWED UNDER THE
 2020 EXISTING BUILDING CODE FOR CHANGE IN OCCUPANCY
 CHAPTER 10, FOR THE LATERAL ADDITION CHAPTER 11 AND THE
 2020 FBC-BUILDING CODE FOR NEW NON-PERMITTED WORK.
 3A) 2ND REQUEST. COVERSHEET COMMENT FROM SHEET A-100
 SITE & LIFE SAFETY PLAN: THE SUBMITTED PLAN INDICATES
 THE BUILDING & LIFE SAFETY INFORMATION WAS DEVELOPED
 UNDER THE 2017 FLORIDA BUILDING CODE. PLEASE BE AWARE
 THAT THE 2020 FLORIDA BUILDING CODE 7TH EDITION WAS
 ADOPTED STATEWIDE ON DEC. 31, 2020. THE PERMIT SET OF
 PLANS WERE SUBMITTED ON 02/14/2022. PLEASE UPDATE THE
 PLANS.
  
 3B) 2ND REQUEST. THE ISSUE IS NOT THAT SHEET A-100 IS
 NO LONGER APPLICABLE, THE STATEMENT THE VIP MODULAR
 BUILDINGS AND 8 TRAILERS HAVE BEEN REMOVED FROM THE
 PLANS, THE ISSUE IS ARE THESE UNITS STILL AT THE SITE
 AND PART OF THE UNPERMITTED WORK.
 1ST ROUND OF COMMENTS. THE SITE PLAN & LIFE SAFETY PLAN
 SHOWS THE VIP MODULAR BUILDING AND 8 TRAILERS ON SITE,
 MANY OF THESE ARE ALSO MODULAR BUILDINGS THAT HAVE NOT
 APPLIED FOR PERMITS, WHY HAS NO PERMIT BEEN APPLIED
 FOR? 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 105.1 PERMITS.
  
 3C-J) COMPLIED.
  
  
 3K) 2ND REQUEST. SHEET A1-2 NOTES 8. 2020 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.2.1. DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES "CODE SECTIONS SHALL NOT BE CITED AS A
 WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
 SHEET A-1-2 SITE & LIFE SAFETY PLAN. PLEASE PROVIDE
 COMPLIANCE WITH THE 2020 FBC-BUILD. CODE SECTION 806.3
 COMBUSTIBLE DECORATIVE MATERIALS SECTION 806.3
 EXCEPTION 1.
  
  
 3L) 2ND REQUEST A1.2 NOTE 9. 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1. DRAWINGS & SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC TO THE TECHNICAL CODES
 "CODE SECTIONS SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS
 A SUBSTITUTE FOR SPECIFIC INFORMATION".
 IT WOULD ALSO APPEAR THAT THIS CURTAIN TYPE MATERIAL
 GOES ACROSS THE FRONT OF THE STAGE, IS THIS MATERIAL
 CREATING A PROSCENIUM CURTAIN IN COMPLIANCE WITH
 410.3.5 OF THE 2020 FBC-BUILDING CODE.
  
 3M) COMPLIED.
  
 3N) COMPLIED.
  
 4) COMPLIED.
  
 5A) 2ND REQUEST. A1-2 NON-PERMITTED STAGE CONSIDERED
 NEW CONSTRUCTION, LIFTS HAVE BEEN REMOVED FROM THE
 PROJECT, THE COVERSHEET STATES A OCCUPANT LOAD OF 108
 ON STAGE REQUIRING 2 EXITS AND 2 ACCESSIBLE EXITS. 2020
 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
 NEW BUILDINGS ONLY, SEE EXCEPTIONS IN EXISTING
 BUILDINGS.
 1ST ROUND OF COMMENTS. THERE ARE 2 PROPOSED VERTICAL
 LIFTS ONE A GUEST STAGE ENTRY TO THE STAGE, THE 2ND TO
 THE PROPOSED 2ND FLOOR PRODUCTION ROOM. LULA LIFTS,
 LIMITED USE/ LIMITED APPLICATION ELEVATORS SHALL COMPLY
 WITH SECTION 408 OF THE FL. ACCESSIBILITY CODE AND ASME
 A17.1.
  
 5B) 2ND REQUEST. . A1-2 NON-PERMITTED STAGE CONSIDERED
 NEW CONSTRUCTION, LIFTS HAVE BEEN REMOVED FROM THE
 PROJECT, THE COVERSHEET STATES A OCCUPANT LOAD OF 108
 ON STAGE REQUIRING 2 EXITS AND 2 ACCESSIBLE EXITS. 2020
 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
 NEW BUILDINGS ONLY, SEE EXCEPTIONS IN EXISTING
 BUILDINGS.
 1ST ROUND OF COMMENTS. PLEASE PROVIDE SHOP DRAWINGS FOR
 BOTH OF THE LIFTS. SHOP DRAWINGS ARE TO BE REVIEWED AND
 APPROVED Y THE DESIGNER OF RECORD. FL 61G1-23.015 (2)
 THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.
  
 5C) A1-2 NON-PERMITTED STAGE CONSIDERED NEW
 CONSTRUCTION, LIFTS HAVE BEEN REMOVED FROM THE PROJECT,
 THE COVERSHEET STATES A OCCUPANT LOAD OF 108 ON STAGE
 REQUIRING 2 EXITS AND 2 ACCESSIBLE EXITS. 2020
 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
 NEW BUILDINGS ONLY, SEE EXCEPTIONS IN EXISTING
 BUILDINGS.
 1ST ROUND OF COMMENTS. THE PROPOSED LULA LIFT ON THE
 RIGHT SIDE OF THE PAGE IS NOT IN A 1-HOUR SHAFT GOING
 FROM FLOOR TO FLOOR, THE PROPOSED STAIRWELL IS ENCLOSED
 BUT THE PLANS DO NOT SHOW A 1-HOUR ENCLOSURE. IF THIS
 SHAFT FOR BOTH THE LULA LIFT AND STAIR IS TO BE
 CONSIDERED A EXIT ACCESS STAIRWAY PROVIDE TRAVEL
 DISTANCE IN COMPLIANCE WITH SECTION 1017.3.1 OF THE
 2020 FBC-BUILDING CODE.
  
 5D) 2ND REQUEST. THE LEFT SIDE OF STAGE, NEW REDESIGN
 OF GUEST STAGE ENTRY DOES NOT SHOW 2 ACCESSIBLE EXITS
 FROM THE STAGE, ONLY ONE. STAGE CONSIDERED NEW
 CONSTRUCTION; NO PERMIT PULLED FOR STAGE. 2020
 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
 NEW BUILDINGS ONLY, SEE EXCEPTIONS IN EXISTING
 BUILDINGS.
  
 5E-F) COMPLIED.
  
 6) COMPLIED.
 7-8) COMPLIED, NEW DESIGN
  
 9) 2ND REQUEST. SHEET A2.2 NEW GANGED RESTROOMS:
 9A) WOMENS/MENS/ STAFF RESTROOM, THE INSIDE DIMENSION
 IS 7 FEET, WITH THE WATER CLOSET AT 18 INCHES
 CENTERLINE FROM SIDE WALL AND LAV IS ALSO CENTERLINE AT
 18 INCHES FROM SIDE WALL THIS DIMENSION WILL NOT
 PROVIDE THE 60 INCHES REQUIRED FOR CLEAR FLOOR SPACE
 FOR THE WATER CLOSET. CLEARANCES AT WATER CLOSETS.
 604.3 CLEARANCE. CLEARANCES AROUND THE WATER CLOSETS
 AND IN TOILET COMPARTMENTS SHALL COMPLY WITH 604.3.
 604.3.1. SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM PERPENDICULAR FROM THE REAR
 WALL. PLANS SHOW THE DIMENSIONS BACKWARDS. NOTE THE
 MINIMUM BACK WALL MEASUREMENT SHOULD BE 7-FOOT 1 INCH
 (FINISHES MAY ENCROACH) ON THE FINISH DIMENSION WITH
 LAV AT CENTERLINE 15 INCHES!!!
  
  
 10-12) COMPLIED.
  
 13) SEMI-COMPLIED, SUBMITTED. SHEETS A3-0 & A3-1
 ELEVATIONS. COMPONENTS & CLADDING. PLEASE SUBMIT THE
 COMPONENTS AND CLADDING PRODUCT APPROVALS. 2020 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, & ROOF HATCHES.
 (B) PANEL WALLS: WALL LOUVERS, MULLIONS & EFIS SYSTEMS
 IF USED,
 (C) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS ETC.
  
 14) 2ND REQUEST- ARCHITECT. W. P. B. 107.3.4. PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY
 FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE
 REVIEWED AND APPROVED IN WRITING (SHOP DRAWING STAMP OF
 APPROVAL) BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 15) PROVISO, IF ANY NO RESPONSE. DELEGATED ENGINEERING.
 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL
 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD
 THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF
 RECORD FOR REVIEW.
  
 16) ROOFING:NO PRODUCT APPROVAL WAS SUBMITTED FOR
 ROOFING. 220 FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 17) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 18) 2ND REQUEST. THE STRUCTURAL SHEETS SHOW NEW
 STRUCTURAL ELEMENTS, THIS WILL CREATE THE PROJECT TO BE
 A THRESHOLD BUILDING. THRESHOLD BUILDING / FL S. S.
 553.71(7) THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
  
 18A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN.
  
 18B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE. PLEASE REVIEW THE GUIDELINES
 AND POLICIES FOR PROJECTS CONCERNING THRESHOLD
 INSPECTOR PAGES 1-5, PAGES 6-8 THRESHOLD INSPECTOR
 FORMS.
 E-MAIL SENT WITH ATTACHMENT TO: :
 [email protected] 12/28/2022 8:34 AM.
  
 18C) 2ND REQUEST. THRESHOLD BLDG., REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 18D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
  
 18E) PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 18F) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 19) COMPLIED. SHEET S0.3 COMPONENTS & CLADDING
 ALLOWABLE PRESSURES.
  
 20) COMPLIED. TYPE IIB.
  
 21) COMPLIED.
  
 22) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  