| 2023-06-01 11:55:15 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22020746 |
| | ADD: 2951 ELECTRONICS WAY |
| | CONT: SURFSIDE CONTRACTING/ CGC |
| | TEL: 561-748-6022 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: JUNE 06TH/2023 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST, TO DATE THIS PERMIT HAS NOT BEEN |
| | RESUBMITTED. PERMIT 21111052(EXPIRED) 2951 ELECTRONIC |
| | WAY INSTALL EGRESS DOORS, RAMP, LANDING AND STAIRS NOT |
| | PERMITTED. ON 6/6/2022 APPLICANT NEEDS TO RESUBMIT. |
| | 4XFEE ADDED TO PERMIT. GOOGLE EARTH SHOWS WORK |
| | COMPLETE. THIS WORK HAS TO BE ACCOUNTED FOR BEFORE THIS |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) 2ND REQUEST, STAGE, IT DOES NOT MATTER, IT IS |
| | NON-PERMITTED WORK THERE FOR CONSIDERED NEW WORK. AGAIN |
| | BEFORE THIS PERMIT CAN BE ISSUED, THE STAGE HAS TO MEET |
| | ALL CODE REQUIREMENTS FOR NON-PERMITTED WORK. PERMIT |
| | 22020746 SHEET A2-0 OVERALL FLOOR PLAN- LIFE SAFETY. |
| | NOTE THAT THE EXISTING STAGE AREA TO REMAIN AT +30 |
| | INCHES AFF. PLEASE NOTE THERE WAS NEVER A PERMIT PULLED |
| | FOR THE BUILDING OF THE STAGE OR ANY AREAS BUILT AT 30 |
| | INCHES AFF. THESE AREAS WILL BE TREATED AS NEW |
| | CONSTRUCTION. 2020 EXISTING BUILDING CODE. 801.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. WILL NEED TO |
| | COMPLY WITH THE 2020 FBC-BUILDING SECTION 410, STAGES, |
| | PLATFORMS AND TECHNICAL PRODUCTION AREAS, PROSCENIUM |
| | WALL AND OR CURTAINS, ROOF VENTS SMOKE CONTROL, ETC. |
| | SHEET A4.0 NOTE 6 STATES THE EXISTING STAGE IS |
| | COMPRISED OF ?? INCH PLYWOOD, METAL FRAMING. PLEASE |
| | REVIEW SECTION 410.3.1. EXCEPTION 1, 2-INCH-THICK WOOD |
| | DECK OR 410.4 FIRE- RETARDANT- TREATED WOOD. PLEASE |
| | PROVIDE THE LOAD BEARING COMPACITY OF STAGE IN |
| | COMPLIANCE WITH 2020 FBC-BUILDING TABLE 1607.1. |
| | THE STAGE WILL ALSO NEED TO SHOW COMPLIANCE WITH |
| | 410.3.7 OF THE 2020 FBC-BUILDING CODE. |
| | 2A) NEW COMMENT. COVERSHEET UNDER THE PROJECT DATA LIST |
| | THE CLASSIFICATION OF WORK AS ALTERATION LEVEL 2/ |
| | EXPANSION. THE PROJECT NEEDS TO BE REVIEWED UNDER THE |
| | 2020 EXISTING BUILDING CODE FOR CHANGE IN OCCUPANCY |
| | CHAPTER 10, FOR THE LATERAL ADDITION CHAPTER 11 AND THE |
| | 2020 FBC-BUILDING CODE FOR NEW NON-PERMITTED WORK. |
| | 3A) 2ND REQUEST. COVERSHEET COMMENT FROM SHEET A-100 |
| | SITE & LIFE SAFETY PLAN: THE SUBMITTED PLAN INDICATES |
| | THE BUILDING & LIFE SAFETY INFORMATION WAS DEVELOPED |
| | UNDER THE 2017 FLORIDA BUILDING CODE. PLEASE BE AWARE |
| | THAT THE 2020 FLORIDA BUILDING CODE 7TH EDITION WAS |
| | ADOPTED STATEWIDE ON DEC. 31, 2020. THE PERMIT SET OF |
| | PLANS WERE SUBMITTED ON 02/14/2022. PLEASE UPDATE THE |
| | PLANS. |
| | |
| | 3B) 2ND REQUEST. THE ISSUE IS NOT THAT SHEET A-100 IS |
| | NO LONGER APPLICABLE, THE STATEMENT THE VIP MODULAR |
| | BUILDINGS AND 8 TRAILERS HAVE BEEN REMOVED FROM THE |
| | PLANS, THE ISSUE IS ARE THESE UNITS STILL AT THE SITE |
| | AND PART OF THE UNPERMITTED WORK. |
| | 1ST ROUND OF COMMENTS. THE SITE PLAN & LIFE SAFETY PLAN |
| | SHOWS THE VIP MODULAR BUILDING AND 8 TRAILERS ON SITE, |
| | MANY OF THESE ARE ALSO MODULAR BUILDINGS THAT HAVE NOT |
| | APPLIED FOR PERMITS, WHY HAS NO PERMIT BEEN APPLIED |
| | FOR? 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 105.1 PERMITS. |
| | |
| | 3C-J) COMPLIED. |
| | |
| | |
| | 3K) 2ND REQUEST. SHEET A1-2 NOTES 8. 2020 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION 107.2.1. DRAWINGS & SPECIFICATIONS |
| | SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR |
| | OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE |
| | QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL |
| | CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE |
| | TECHNICAL CODES "CODE SECTIONS SHALL NOT BE CITED AS A |
| | WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". |
| | SHEET A-1-2 SITE & LIFE SAFETY PLAN. PLEASE PROVIDE |
| | COMPLIANCE WITH THE 2020 FBC-BUILD. CODE SECTION 806.3 |
| | COMBUSTIBLE DECORATIVE MATERIALS SECTION 806.3 |
| | EXCEPTION 1. |
| | |
| | |
| | 3L) 2ND REQUEST A1.2 NOTE 9. 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1. DRAWINGS & SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC TO THE TECHNICAL CODES |
| | "CODE SECTIONS SHALL NOT BE CITED AS A WHOLE OR IN |
| | PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS |
| | A SUBSTITUTE FOR SPECIFIC INFORMATION". |
| | IT WOULD ALSO APPEAR THAT THIS CURTAIN TYPE MATERIAL |
| | GOES ACROSS THE FRONT OF THE STAGE, IS THIS MATERIAL |
| | CREATING A PROSCENIUM CURTAIN IN COMPLIANCE WITH |
| | 410.3.5 OF THE 2020 FBC-BUILDING CODE. |
| | |
| | 3M) COMPLIED. |
| | |
| | 3N) COMPLIED. |
| | |
| | 4) COMPLIED. |
| | |
| | 5A) 2ND REQUEST. A1-2 NON-PERMITTED STAGE CONSIDERED |
| | NEW CONSTRUCTION, LIFTS HAVE BEEN REMOVED FROM THE |
| | PROJECT, THE COVERSHEET STATES A OCCUPANT LOAD OF 108 |
| | ON STAGE REQUIRING 2 EXITS AND 2 ACCESSIBLE EXITS. 2020 |
| | FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS |
| | SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | NEW BUILDINGS ONLY, SEE EXCEPTIONS IN EXISTING |
| | BUILDINGS. |
| | 1ST ROUND OF COMMENTS. THERE ARE 2 PROPOSED VERTICAL |
| | LIFTS ONE A GUEST STAGE ENTRY TO THE STAGE, THE 2ND TO |
| | THE PROPOSED 2ND FLOOR PRODUCTION ROOM. LULA LIFTS, |
| | LIMITED USE/ LIMITED APPLICATION ELEVATORS SHALL COMPLY |
| | WITH SECTION 408 OF THE FL. ACCESSIBILITY CODE AND ASME |
| | A17.1. |
| | |
| | 5B) 2ND REQUEST. . A1-2 NON-PERMITTED STAGE CONSIDERED |
| | NEW CONSTRUCTION, LIFTS HAVE BEEN REMOVED FROM THE |
| | PROJECT, THE COVERSHEET STATES A OCCUPANT LOAD OF 108 |
| | ON STAGE REQUIRING 2 EXITS AND 2 ACCESSIBLE EXITS. 2020 |
| | FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS |
| | SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | NEW BUILDINGS ONLY, SEE EXCEPTIONS IN EXISTING |
| | BUILDINGS. |
| | 1ST ROUND OF COMMENTS. PLEASE PROVIDE SHOP DRAWINGS FOR |
| | BOTH OF THE LIFTS. SHOP DRAWINGS ARE TO BE REVIEWED AND |
| | APPROVED Y THE DESIGNER OF RECORD. FL 61G1-23.015 (2) |
| | THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND |
| | REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC. |
| | |
| | 5C) A1-2 NON-PERMITTED STAGE CONSIDERED NEW |
| | CONSTRUCTION, LIFTS HAVE BEEN REMOVED FROM THE PROJECT, |
| | THE COVERSHEET STATES A OCCUPANT LOAD OF 108 ON STAGE |
| | REQUIRING 2 EXITS AND 2 ACCESSIBLE EXITS. 2020 |
| | FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS |
| | SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | NEW BUILDINGS ONLY, SEE EXCEPTIONS IN EXISTING |
| | BUILDINGS. |
| | 1ST ROUND OF COMMENTS. THE PROPOSED LULA LIFT ON THE |
| | RIGHT SIDE OF THE PAGE IS NOT IN A 1-HOUR SHAFT GOING |
| | FROM FLOOR TO FLOOR, THE PROPOSED STAIRWELL IS ENCLOSED |
| | BUT THE PLANS DO NOT SHOW A 1-HOUR ENCLOSURE. IF THIS |
| | SHAFT FOR BOTH THE LULA LIFT AND STAIR IS TO BE |
| | CONSIDERED A EXIT ACCESS STAIRWAY PROVIDE TRAVEL |
| | DISTANCE IN COMPLIANCE WITH SECTION 1017.3.1 OF THE |
| | 2020 FBC-BUILDING CODE. |
| | |
| | 5D) 2ND REQUEST. THE LEFT SIDE OF STAGE, NEW REDESIGN |
| | OF GUEST STAGE ENTRY DOES NOT SHOW 2 ACCESSIBLE EXITS |
| | FROM THE STAGE, ONLY ONE. STAGE CONSIDERED NEW |
| | CONSTRUCTION; NO PERMIT PULLED FOR STAGE. 2020 |
| | FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS |
| | SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | NEW BUILDINGS ONLY, SEE EXCEPTIONS IN EXISTING |
| | BUILDINGS. |
| | |
| | 5E-F) COMPLIED. |
| | |
| | 6) COMPLIED. |
| | 7-8) COMPLIED, NEW DESIGN |
| | |
| | 9) 2ND REQUEST. SHEET A2.2 NEW GANGED RESTROOMS: |
| | 9A) WOMENS/MENS/ STAFF RESTROOM, THE INSIDE DIMENSION |
| | IS 7 FEET, WITH THE WATER CLOSET AT 18 INCHES |
| | CENTERLINE FROM SIDE WALL AND LAV IS ALSO CENTERLINE AT |
| | 18 INCHES FROM SIDE WALL THIS DIMENSION WILL NOT |
| | PROVIDE THE 60 INCHES REQUIRED FOR CLEAR FLOOR SPACE |
| | FOR THE WATER CLOSET. CLEARANCES AT WATER CLOSETS. |
| | 604.3 CLEARANCE. CLEARANCES AROUND THE WATER CLOSETS |
| | AND IN TOILET COMPARTMENTS SHALL COMPLY WITH 604.3. |
| | 604.3.1. SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE |
| | 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES MINIMUM PERPENDICULAR FROM THE REAR |
| | WALL. PLANS SHOW THE DIMENSIONS BACKWARDS. NOTE THE |
| | MINIMUM BACK WALL MEASUREMENT SHOULD BE 7-FOOT 1 INCH |
| | (FINISHES MAY ENCROACH) ON THE FINISH DIMENSION WITH |
| | LAV AT CENTERLINE 15 INCHES!!! |
| | |
| | |
| | 10-12) COMPLIED. |
| | |
| | 13) SEMI-COMPLIED, SUBMITTED. SHEETS A3-0 & A3-1 |
| | ELEVATIONS. COMPONENTS & CLADDING. PLEASE SUBMIT THE |
| | COMPONENTS AND CLADDING PRODUCT APPROVALS. 2020 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS, & ROOF HATCHES. |
| | (B) PANEL WALLS: WALL LOUVERS, MULLIONS & EFIS SYSTEMS |
| | IF USED, |
| | (C) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| | CONCRETE INSULATION, ROOF TOP VENTILATORS ETC. |
| | |
| | 14) 2ND REQUEST- ARCHITECT. W. P. B. 107.3.4. PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY |
| | FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING (SHOP DRAWING STAMP OF |
| | APPROVAL) BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 15) PROVISO, IF ANY NO RESPONSE. DELEGATED ENGINEERING. |
| | 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL |
| | 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD |
| | THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF |
| | RECORD FOR REVIEW. |
| | |
| | 16) ROOFING:NO PRODUCT APPROVAL WAS SUBMITTED FOR |
| | ROOFING. 220 FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| | ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| | BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| | COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| | CALCULATION PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |
| | 17) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 18) 2ND REQUEST. THE STRUCTURAL SHEETS SHOW NEW |
| | STRUCTURAL ELEMENTS, THIS WILL CREATE THE PROJECT TO BE |
| | A THRESHOLD BUILDING. THRESHOLD BUILDING / FL S. S. |
| | 553.71(7) THRESHOLD BUILDING" MEANING ANY BUILDING |
| | WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, |
| | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS |
| | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 |
| | SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN |
| | 500 PERSONS. |
| | |
| | 18A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN. |
| | |
| | 18B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT |
| | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| | REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE |
| | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE |
| | THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT |
| | BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO |
| | THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT |
| | ISSUANCE WILL TAKE PLACE. PLEASE REVIEW THE GUIDELINES |
| | AND POLICIES FOR PROJECTS CONCERNING THRESHOLD |
| | INSPECTOR PAGES 1-5, PAGES 6-8 THRESHOLD INSPECTOR |
| | FORMS. |
| | E-MAIL SENT WITH ATTACHMENT TO: : |
| | [email protected] 12/28/2022 8:34 AM. |
| | |
| | 18C) 2ND REQUEST. THRESHOLD BLDG., REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 18D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE |
| | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS |
| | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL |
| | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL |
| | OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE |
| | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. |
| | UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED |
| | FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. |
| | |
| | 18E) PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 18F) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | |
| | 19) COMPLIED. SHEET S0.3 COMPONENTS & CLADDING |
| | ALLOWABLE PRESSURES. |
| | |
| | 20) COMPLIED. TYPE IIB. |
| | |
| | 21) COMPLIED. |
| | |
| | 22) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |