Plan Review Notes
Plan Review Notes For Permit 22020746
Permit Number 22020746
Review Stop P
Sequence Number 1
Notes
Date Text
2022-12-07 16:05:311ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22070746
 12/7/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P200: PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 COMPLIANCE WITH SEC. 1010.1 FBC EX, AND TABLE 403.1 FBC
 P. PROVIDE A SCHEDULE THAT SHOWS THE REQUIRED AND
 PROVIDED NUMBER OF FIXTURES.
  
 2) P201: PROVIDE THE CORRELATING TEXT THAT GOES WITH
 KEYNOTE #10- SEC. 107.2.1 WPB.
  
 3) P400: THE PLAN SHOWS PRIMARY ROOF DRAINAGE BUT NOT
 SECONDARY OR OVERFLOW AS REQUIRED BY SEC. 1108.1,
 1108.2, & 1008.3 FBC P. PLEASE REFER TO SEC. 1503.4.2.1
 FBC B OVERFLOW SCUPPERS. WHEN OTHER MEANS OF DRAINAGE
 OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW SCUPPERS
 SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS THAN 2
 INCHES NOR MORE THAN 4 INCHES ABOVE THE FINISHED ROOF
 COVERING AND SHALL BE LOCATED AS CLOSE AS PRACTICAL TO
 REQUIRED VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND
 PARAPET SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 A) P400: PLEASE INDICATE HOW THE STORMWATER FROM THE
 PRIMARY SCUPPERS WILL BE CONVEYED AWAY FROM THE
 BUILDING TO AN APPROVED PLACE OF DISPOSAL- SEC. 1108.2
 FBC P.
  
 4) P600, P701 WATER HEATER DETAIL: PROVIDE A MASTER
 THERMOSTATIC MIXING VALVE AT THE WATER HEATER- SEC.
 607.1.1 FBC P. PLEASE REVISE THE DRAWING TO SHOW
 LOCATION AND PIPING CONNECTIONS.
 A) P600, P701: PLEASE REVIEW SEC. 607.2.2. PIPING FOR
 RECIRCULATION SYSTEMS HAVING MASTER THERMOSTATIC
 VALVES. WHERE A THERMOSTATIC MIXING VALVE IS USED IN A
 SYSTEM WITH A HOT WATER RECIRCULATING PUMP, THE HOT
 WATER OR TEMPERED WATER RETURN LINE SHALL BE ROUTED TO
 THE COLD WATER INLET PIPE OF THE WATER HEATER AND THE
 COLD WATER INLET PIPE OR THE HOT WATER RETURN
 CONNECTION OF THE THERMOSTATIC MIXING VALVE- SEC.
 607.2.2 FBC P. PLEASE REVISE THE DRAWING TO SHOW
 LOCATION AND PIPING CONNECTIONS.
  
 5) P701 WATER RISER: REFER TO SEC. C404.5.1 FBC ENERGY.
 THE 1/2-INCH HW FIXTURE SUPPLY PIPES ARE EXCEEDING
 THEIR 2FT. ALLOWABLE PIPING LENGTHS FROM THE NEAREST HW
 SOURCES. THIS CAN BE CORRECTED BY PROVIDING HWR LOOPS
 FOR EACH BRANCH LINE SUPPLYING LAVATORIES, OR BY
 PROVIDING POINT OF USE WATER HEATERS.
  
 6) P701: PLEASE SHOW THE MEANS OF PROVIDING TEMPERED
 WATER DELIVERY FROM THE PUBLIC LAVATORIES PER SEC.
 419.5 FBC P. A TYPICAL SOLUTION WOULD BE TO PROVIDE
 ASSE 1070 APPROVED MIXING VALVES AT EACH LAV- SEE SEC.
 607.1.2 FBC P.
  
 7) P800: PROVIDE A PLUMBING FIXTURE SCHEDULE INDICATING
 MAKES AND MODELS OF THE WATER CLOSETS, LAVATORIES,
 FAUCETS, DRINKING FOUNTAINS, SHOWER AND SHOWER
 CONTROLS, AND SERVICE SINK- SEC. 404 & 405 FBC P.
  
 8) P000: REFER TO THE FBC ENERGY CONSERVATION CODE-
 2020 AND UPDATE THE OUTDATED CODE REFERENCES AND TABLES
 SHOWN IN THE DOMESTIC HOT WATER SYSTEM NOTES. REFER TO
 TABLE C403. 2.10 FBC EC AND PROVIDE THE TYPE AND
 THICKNESS OF HW PIPE INSULATION.
  
 9) SHEETS A2.1, A2.2, A2.3 PLEASE PROVIDE ENLARGED
 ACCESSIBLE BATHROOM DETAILS SHOWING COMPLIANCE WITH THE
 FOLLOWING FBC ACC CODE SECTIONS.
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOOR- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2
 SHOWER:
 L) PLEASE SHOW THE SHOWER DIMENSIONS, AND THE CLEAR
 FLOOR SPACE DIAGRAM AND DIMENSIONS- SECTION 608.2.2.
 PLEASE NOTE THE WATER CLOSER IS OBSTRUCTING THE
 REQUIRED CLEAR FLOOR SPACE FOR THE SHOWER. REFER TO
 SEC. 608.2.2.1: A 30 INCH WIDE MINIMUM BY 60 INCH LONG
 MINIMUM CLEARANCE SHALL BE PROVIDED ADJACENT TO THE
 OPEN FACE OF THE SHOWER COMPARTMENT.
 EXCEPTION: A LAVATORY COMPLYING WITH 606 SHALL BE
 PERMITTED ON ONE 30 INCH WIDE MINIMUM SIDE OF THE
 CLEARANCE PROVIDED THAT IT IS NOT ON THE SIDE OF THE
 CLEARANCE ADJACENT TO THE CONTROLS OR, WHERE PROVIDED,
 NOT ON THE SIDE OF THE CLEARANCE ADJACENT TO THE SHOWER
 SEAT.
 M) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND
 608.3.2.
 N) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SECTION 608.5.2.
 O) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6.
 P) LOCATION OF ACCESSIBLE SHOWER SEAT- SECTIONS 610.3 &
 610.3.2.
 Q) PLEASE NOTE THE THRESHOLD FOR THE NEW ROLL-IN SHOWER
 SHALL BE 1/2-INCH HIGH MAXIMUM- SEC. 608.7
  
 DRINKING FOUNTAINS:
 R) REFER TO SECTIONS 306, 307, AND 602 FBC ACC AND
 PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND
 ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT
 HEIGHTS, AND SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48
 IN. CLEAR FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH
 TO THE FOUNTAIN- SECTION 602.2 FBC ACC.
 S) PLEASE NOTE THE LOCATIONS OF THE FOUNTAINS ARE NOT
 IN COMPLIANCE WITH SECTION 307.2 PROTRUSION LIMITS.
 PLEASE LOCATE THE FIXTURES IN A NICHE OR PROVIDE A WING
 WALL ON THE OPEN SIDE PROTRUSION.
  
 BREAKROOM
 T) SHOW THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS
 FOR THE SINK- SEC. 606.2.
 U) HEIGHT OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTION 606.3.
  
  
 10) A2.2: PLEASE REFER TO SEC. 213.3.1 AND PROVIDE A
 MINIMUM OF ONE MALE AND ONE FEMALE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT PER SEC. 604.8.2 FBC ACC.
 PLEASE SHOW THE LOCATIONS OF THE COMPARTMENT ON THE
 PLAN AND PROVIDE A DETAIL IN COMPLIANCE WITH FIGURE
 604.8.2.
  
 11) A2.2: PROVIDE THE DIMENSIONS OF THE STANDARD WATER
 CLOSET COMPARTMENTS- SEC. 405.3.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  