| 2022-12-13 15:19:58 | 1ST REVIEW FMC |
| | PERMIT: 22020746 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) AS THIS PROJECT HAS GONE FROM A STORAGE OCCUPANCY |
| | WHICH IS EXEMPT FROM THE ENERGY CODE TO AN ASSEMBLY |
| | OCCUPANCY PLEASE PROVIDE THE ENERGY CALCULATIONS FOR |
| | THIS PROJECT TO SHOW THE ENERGY CODE COMPLIANCE. FEC |
| | C402.1 |
| | |
| | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS |
| | FOR THIS PROJECT. FEC C403.2.1 |
| | |
| | 3) REMOVE THE NOTE ON THE DRAWINGS THAT STATES EXISTING |
| | STAGE PLATFORM BELOW AS THIS WOULD NOT BE EXISTING IN A |
| | WAREHOUSE AND WOULD NEED TO BE INCLUDED IN THE CHANGE |
| | OF USE PERMIT AND REVIEW. |
| | |
| | 4) INCLUDE THE REQUIRED FIRE DAMPERS AT EACH DUCT |
| | PENETRATION OF A RATED WALL. FMC 607 |
| | |
| | 5) PLEASE PROVIDE INFORMATION THAT WOULD MEET THE STAGE |
| | VENTILATION REQUIREMENTS OF FBC 410.3.7 |
| | |
| | 6) PLEASE SHOW THE DESIGN MEETS THE ROOF VENTS |
| | REQUIREMENT OF FBC 410.3.7.1 |
| | |
| | 7) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON THE |
| | OCCUPANCY CLASSIFICATIONS AND OCCUPANT DENSITY FROM |
| | TABLE 403.3.1.1 OF THE FMC. FMC 403.3.1.1 |
| | |
| | 8) PROVIDE THE AHU SCHEDULES. FBC 107.3.5 |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |