Plan Review Notes
Plan Review Notes For Permit 22020746
Permit Number 22020746
Review Stop I
Sequence Number 1
Notes
Date Text
2022-03-23 06:53:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEE FBC EXISTING BUILDING 303.1 WHICH STATES "THE
 ALTERATION, CHANGE OF OCCUPANCY, . . . SHALL COMPLY
 WITH ONE OF THE METHODS LISTED IN SECTIONS 301.3.1
 THROUGH 301.3.3 AS SELECTED BY APPLICANT."
  
 A ONE PAGE PLAN WAS SUBMITTED THAT DOES NOT INDICATE
 METHOD OF COMPLIANCE, SO IT IS NOT POSSIBLE FOR PLAN
 REVIEW TO PROVIDE AN ACCURATE CORRECTION LIST WITH CODE
 REFERENCES AS REQUIRED BY FLORIDA STATUTE.
 ADDITIONALLY, SHEET A-100 DECLARES GOVERNING CODE AS
 2017 FBC, BUT GOVERNING CODE IS FBC 2020.
  
 NO INFORMATION WAS PROVIDED FOR MECHANICAL, ELECTRICAL,
 PLUMBING, ACCESSIBILITY. SEE FBC 107.1 THROUGH 107.3.5.
  
 NO INFORMATION IS SHOWN ON THE PLAN AS TO WHAT IS
 EXISTING, WHAT IS NEW. A ROOM MARKED "HVAC" IS SHOWN,
 NO MECHANICAL PLANS SUBMITTED. ASSEMBLY THEATER STYLE
 SEATING IS SHOWN, NO DIMENSIONS OR DETAILS. IT APPEARS
 THERE WILL BE A STAGE WITH STAIRS, NO RAMPS SHOWN. A
 "VIP TRAILER" IS SHOWN, NO DETAILS. THERE IS A NOTE ON
 THE PLAN LABELED "EGRESS" WHICH APPEARS TO BE THE EXIT
 DISCHARGE TO THE PUBLIC WAY, BUT THERE APPEAR TO BE
 OBSTRUCTIONS WHICH ARE NOT IDENTIFIED.
  
 THERE ARE ROOMS ON THE PLAN WHICH ARE LABELED BUT NOT
 CLEAR AS TO FUNCTION - EGOSQUE, GREENROOM, AMT, KINRGY.
 EACH ROOM SHOULD BE LABELED AND CLEAR AS TO OCCUPANCY
 CLASSIFICATION, USE, AND OCCUPANT LOAD.
  
 NONE OF THE DOORS ARE LABELED WITH DOOR IDENTIFYING
 NUMBERS SO IT IS DIFFICULT TO PROVIDE A CURSORY REVIEW.
 THERE ARE INSWINGING DOORS, NO OCCUPANT LOAD, NO DOOR
 WIDTH. LOUNG, EGOSQUE, ETC. MEANS OF EGRESS GO THROUGH
 A HALLWAY WHICH HAS NO DIMENSIONS, INSWING DOOR. SINCE
 NO OCCUPANT LOAD WAS PROVIDED FOR THE FOUR ROOMS, ALSO
 NO DIMENSIONS FOR THE FOUR ROOMS, IT CANNOT BE
 DETERMINED IF AN INSWING DOOR IS PERMITTIED. IT LEADS
 TO AN AREA WHICH APPEARS TO BE THE THEATER, A
 CORRUGATED STYLE LINE AROUND THAT AREA, NO INDICATION
 OF WHAT THAT LINE IS AND NO DIMENSION FOR WHAT APPEARS
 TO BE A HALLWAY.
  
 ALSO SEE FBC 2020 ACCESSIBLITY. ALL NEW ELEMENTS ARE TO
 COMPLY AS FOR NEW CONSTRUCTION, SEE FBC A 202.3.
  
 THERE IS A STATEMENT ON THE PLAN THAT STATES
 (PARAPHRASING) THAT THE WAREHOUSE WILL BE UPGRADED IN
 "ACCORDANCE TO REQUIRED CODES AND COMMENTS". THE
 DESIGN, COMPLIANCE WITH THE FLORIDA BUILDING CODE, IS
 THE RESPONSIBILITY OF THE DESIGN PROFESSIONAL. THE
 DESIGN PROFESSIONAL SHALL SELECT THE METHOD OF
 COMPLIANCE IN THE FLORIDA BUILDING CODE 2020, EXISTING
 BUILDING (AS WELL AS OTHER GOVERNING CODES SUCH AS
 FFPC, CITY OF WEST PALM BEACH MUNICIPAL CODE, ETC.).
 THE EXISTING BUILDING CODE IS VERY FLEXIBLE, DESIGNED
 TO GIVE OPTIONS BASED ON THE SPECIFIC PROJECT. THIS IS
 NOT SOMETHING THAT PLAN REVIEW CAN DO FOR THE
 APPLICANT.
  
 AFTER SELECTING THE METHOD OF COMPLIANCE, A PLAN THAT
 COMPLIES WITH ALL REQUIREMENTS OF THE FLORIDA BUILDING
 CODE IS REQUIRED. COMPLIANCE WITH MECHANICAL,
 ELECTRICAL, PLUMBING, BUILDING, ENERGY, ACCESSIBLITY IS
 REQUIRED.
  
 IF THE ARCHITECT HAS SPECIFIC QUESTIONS THAT REQUIRE AN
 INTERPRETATION, HE CAN CONTACT ME. AT THIS TIME THE
 PLAN IS TOO CONCEPTUAL FOR A COMPREHENSIVE PLAN REVIEW.
  
 2. THE DOCUMENT THAT WAS PUT IN THE SIGNATURE FOLDER
 HAS BEEN DELETED. SEE PROJECTDOX INSTRUCTIONS,
 DOCUMENTS SHOULD BE UPLOADED TO DRAWINGS FOLDER AND
 SUPPORTING DOCS ONLY.
  
 3. VALUE APPEARS LOW FBC 109. PRIOR TO ISSUANCE,
 PROVIDE A REASONABLE VALUE. AS SCOPE IS NOT DETERMINED
 VALUE CAN REMAIN AS IS FOR NOW, CONTRACTOR APPLICATION
 TO PROVIDE AN ACCURATE VALUE.
  
  
  