| 2022-03-23 06:53:45 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. SEE FBC EXISTING BUILDING 303.1 WHICH STATES "THE |
| | ALTERATION, CHANGE OF OCCUPANCY, . . . SHALL COMPLY |
| | WITH ONE OF THE METHODS LISTED IN SECTIONS 301.3.1 |
| | THROUGH 301.3.3 AS SELECTED BY APPLICANT." |
| | |
| | A ONE PAGE PLAN WAS SUBMITTED THAT DOES NOT INDICATE |
| | METHOD OF COMPLIANCE, SO IT IS NOT POSSIBLE FOR PLAN |
| | REVIEW TO PROVIDE AN ACCURATE CORRECTION LIST WITH CODE |
| | REFERENCES AS REQUIRED BY FLORIDA STATUTE. |
| | ADDITIONALLY, SHEET A-100 DECLARES GOVERNING CODE AS |
| | 2017 FBC, BUT GOVERNING CODE IS FBC 2020. |
| | |
| | NO INFORMATION WAS PROVIDED FOR MECHANICAL, ELECTRICAL, |
| | PLUMBING, ACCESSIBILITY. SEE FBC 107.1 THROUGH 107.3.5. |
| | |
| | NO INFORMATION IS SHOWN ON THE PLAN AS TO WHAT IS |
| | EXISTING, WHAT IS NEW. A ROOM MARKED "HVAC" IS SHOWN, |
| | NO MECHANICAL PLANS SUBMITTED. ASSEMBLY THEATER STYLE |
| | SEATING IS SHOWN, NO DIMENSIONS OR DETAILS. IT APPEARS |
| | THERE WILL BE A STAGE WITH STAIRS, NO RAMPS SHOWN. A |
| | "VIP TRAILER" IS SHOWN, NO DETAILS. THERE IS A NOTE ON |
| | THE PLAN LABELED "EGRESS" WHICH APPEARS TO BE THE EXIT |
| | DISCHARGE TO THE PUBLIC WAY, BUT THERE APPEAR TO BE |
| | OBSTRUCTIONS WHICH ARE NOT IDENTIFIED. |
| | |
| | THERE ARE ROOMS ON THE PLAN WHICH ARE LABELED BUT NOT |
| | CLEAR AS TO FUNCTION - EGOSQUE, GREENROOM, AMT, KINRGY. |
| | EACH ROOM SHOULD BE LABELED AND CLEAR AS TO OCCUPANCY |
| | CLASSIFICATION, USE, AND OCCUPANT LOAD. |
| | |
| | NONE OF THE DOORS ARE LABELED WITH DOOR IDENTIFYING |
| | NUMBERS SO IT IS DIFFICULT TO PROVIDE A CURSORY REVIEW. |
| | THERE ARE INSWINGING DOORS, NO OCCUPANT LOAD, NO DOOR |
| | WIDTH. LOUNG, EGOSQUE, ETC. MEANS OF EGRESS GO THROUGH |
| | A HALLWAY WHICH HAS NO DIMENSIONS, INSWING DOOR. SINCE |
| | NO OCCUPANT LOAD WAS PROVIDED FOR THE FOUR ROOMS, ALSO |
| | NO DIMENSIONS FOR THE FOUR ROOMS, IT CANNOT BE |
| | DETERMINED IF AN INSWING DOOR IS PERMITTIED. IT LEADS |
| | TO AN AREA WHICH APPEARS TO BE THE THEATER, A |
| | CORRUGATED STYLE LINE AROUND THAT AREA, NO INDICATION |
| | OF WHAT THAT LINE IS AND NO DIMENSION FOR WHAT APPEARS |
| | TO BE A HALLWAY. |
| | |
| | ALSO SEE FBC 2020 ACCESSIBLITY. ALL NEW ELEMENTS ARE TO |
| | COMPLY AS FOR NEW CONSTRUCTION, SEE FBC A 202.3. |
| | |
| | THERE IS A STATEMENT ON THE PLAN THAT STATES |
| | (PARAPHRASING) THAT THE WAREHOUSE WILL BE UPGRADED IN |
| | "ACCORDANCE TO REQUIRED CODES AND COMMENTS". THE |
| | DESIGN, COMPLIANCE WITH THE FLORIDA BUILDING CODE, IS |
| | THE RESPONSIBILITY OF THE DESIGN PROFESSIONAL. THE |
| | DESIGN PROFESSIONAL SHALL SELECT THE METHOD OF |
| | COMPLIANCE IN THE FLORIDA BUILDING CODE 2020, EXISTING |
| | BUILDING (AS WELL AS OTHER GOVERNING CODES SUCH AS |
| | FFPC, CITY OF WEST PALM BEACH MUNICIPAL CODE, ETC.). |
| | THE EXISTING BUILDING CODE IS VERY FLEXIBLE, DESIGNED |
| | TO GIVE OPTIONS BASED ON THE SPECIFIC PROJECT. THIS IS |
| | NOT SOMETHING THAT PLAN REVIEW CAN DO FOR THE |
| | APPLICANT. |
| | |
| | AFTER SELECTING THE METHOD OF COMPLIANCE, A PLAN THAT |
| | COMPLIES WITH ALL REQUIREMENTS OF THE FLORIDA BUILDING |
| | CODE IS REQUIRED. COMPLIANCE WITH MECHANICAL, |
| | ELECTRICAL, PLUMBING, BUILDING, ENERGY, ACCESSIBLITY IS |
| | REQUIRED. |
| | |
| | IF THE ARCHITECT HAS SPECIFIC QUESTIONS THAT REQUIRE AN |
| | INTERPRETATION, HE CAN CONTACT ME. AT THIS TIME THE |
| | PLAN IS TOO CONCEPTUAL FOR A COMPREHENSIVE PLAN REVIEW. |
| | |
| | 2. THE DOCUMENT THAT WAS PUT IN THE SIGNATURE FOLDER |
| | HAS BEEN DELETED. SEE PROJECTDOX INSTRUCTIONS, |
| | DOCUMENTS SHOULD BE UPLOADED TO DRAWINGS FOLDER AND |
| | SUPPORTING DOCS ONLY. |
| | |
| | 3. VALUE APPEARS LOW FBC 109. PRIOR TO ISSUANCE, |
| | PROVIDE A REASONABLE VALUE. AS SCOPE IS NOT DETERMINED |
| | VALUE CAN REMAIN AS IS FOR NOW, CONTRACTOR APPLICATION |
| | TO PROVIDE AN ACCURATE VALUE. |
| | |
| | |
| | |