| Plan Review Notes For Permit 22020688 |
| Permit Number |
22020688 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-03-31 06:03:02 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | THE SHUTTER SCHEDULE IS INCOMPLETE AND CORRECTIONS NEED | | | TO BE MADE, SEE BELOW: | | | | | | 1.) COLUMN #3 (PRESSURES) NEEDS TO BE COMPLETED, THE | | | TOP SECTION IS FOR POSITIVE AND THE BOTTOM SECTION IS | | | FOR NEGATIVE. | | | 2.) COLUMN #5 (SHUTTER GLASS SEPARATION) ENTER VALUE | | | PER PRODUCT APPROVAL. | | | 3.) COLUMN #6 (SHUTTER SPAN), FOR ACCORDIAN SHUTTER | | | SPANS THE SPAN IS TYPICALLY THE HEIGHT FROM TRACK TO | | | TRACK. PLEASE CORRECT THIS SPACE. | | | 4.) COLUMN #7 (SHUTTER ORIENTATION), THIS SHOULD BE | | | VERTICAL LIKE THE SPAN. | | | 5.) COLUMN #11 (SUBSTRATE), THE SUBSTRATE NEEDS TO BE | | | IDENTIFIED. |
|