2022-05-11 09:02:46PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: VALUE ADJUSTED TO $64,287 BASED ON THE ICC
 BUILDING VALUATION DATA. CT
  
 1. PROVIDE A SITE DRAINAGE PLAN WITH A BOUNDARY LINE
 SURVEY PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 2.PROVIDE THE FINISH FLOOR ELEVATION ? NON-FLOOD ZONE
 R403.1.7.3 FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 3. PROVIDE AN ENERGY SUBMITTAL ? RESIDENTIAL (RE)
 R401.2COMPLIANCE.
 PROJECTS SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1. 1.SECTIONS R401 THROUGH R404.
 2. 2.SECTION R405 AND THE PROVISIONS OF SECTIONS R401
 THROUGH R404 LABELED ?MANDATORY.?
  
 4. PLEASE PROVIDE WINDOW AND/OR DOOR SCHEDULES WITH THE
 FOLLOWING INFORMATION:
 1. LOCATION REFERENCE TO OPENING NUMBER ON PLAN.
 2. DEVICE TYPE WINDOW/DOOR/SHUTTER
 3. ROUGH OPENING WXH (AREA SF)
 4. DESIGN PRESSURES TABLE R301.1.(2) OR ASCE 7-16
 5. NOA OR FL NUMBER
 6. MAX DESIGN PRESSURE FROM NOA OR FL
 7. IDENTIFY EGRESS OPENINGS
  
 5.PROVIDE A ROOF SHEATHING FASTENER SCHEDULE PER
 CALCULATED DESIGN PRESSURES ON PLAN PAGE A-2.
 TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING
 SCHEDULE FOR WOOD STRUCTURAL PANELS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  
  