2022-03-08 09:34:49CODES IN EFFECT:
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-3
  
 1) PANEL HAS A NOTE REQUIRING THE NEUTRAL AND GROUND BE
 BONDED?
  
 250.24 LOAD-SIDE GROUNDING CONNECTIONS. A GROUNDED
 CONDUCTOR SHALL NOT BE CONNECTED TO NORMALLY
 NON?CURRENT-CARRYING
 METAL PARTS OF EQUIPMENT, TO EQUIPMENT GROUNDING
 CONDUCTOR(S), OR BE RECONNECTED TO GROUND ON THE LOAD
 SIDE OF THE
 SERVICE DISCONNECTING MEANS EXCEPT AS OTHERWISE
 PERMITTED IN THIS ARTICLE.
  
 2) GROUND ROD SHOWN AT PANEL TO BE BONDED TO SYSTEM
 GROUNDING ELECTRODE CONDUCTOR SYSTEM AT THE SERVICE.
  
 250.58 COMMON GROUNDING ELECTRODE. WHERE AN AC SYSTEM
 IS CONNECTED TO A GROUNDING ELECTRODE IN OR AT A
 BUILDING OR STRUCTURE,
 THE SAME ELECTRODE SHALL BE USED TO GROUND CONDUCTOR
 ENCLOSURES AND EQUIPMENT IN OR ON THAT BUILDING OR
 STRUCTURE.
 WHERE SEPARATE SERVICES, FEEDERS, OR BRANCH CIRCUITS
 SUPPLY A BUILDING AND ARE REQUIRED TO BE CONNECTED TO A
 GROUNDING ELECTRODE(
 S), THE SAME GROUNDING ELECTRODE(S) SHALL BE USED. TWO
 OR MORE GROUNDING ELECTRODES THAT ARE BONDED TOGETHER
 SHALL BE CONSIDERED AS A SINGLE GROUNDING ELECTRODE
 SYSTEM IN THIS SENSE.
  
 3) FAULT CURRENT CALCULATION REQUIRED FOR THE SERVCE
 110.9, 110.10, 110.24(A)
  
 110.24 AVAILABLE FAULT CURRENT. (A) FIELD MARKING.
 SERVICE EQUIPMENT AT OTHER THAN DWELLING
 UNITS SHALL BE LEGIBLY MARKED IN THE FIELD WITH THE
 MAXIMUM AVAILABLE FAULT CURRENT. THE FIELD MARKING(S)
 SHALL INCLUDE THE
 DATE THE FAULT-CURRENT CALCULATION WAS PERFORMED AND BE
 OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
 INVOLVED.
 THE CALCULATION SHALL BE DOCUMENTED AND MADE AVAILABLE
 TO THOSE AUTHORIZED TO DESIGN, INSTALL, INSPECT,
 MAINTAIN, OR OPERATE
 THE SYSTEM.