| 2022-03-02 16:32:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS NO INDICATION OF WHERE IS PROPOSED COOLER | | | IS LOCATED WITHIN THE BUILDING. | | | | | | FOR THE OFFICAIL RECORD AND CONFIRMATION, PLEASE | | | PROVIDE A FLOOR PLAN SHOWING WHERE THIS IS PROPOSED. | | | | | | | | | | | | 2) THERE IS NO INDICATION OF PROVIDING FIRE SPRINKLER | | | PROTECTION WITHIN THE COOLER AS REQUIRED PER NFPA 13 IN | | | BUILDING PROTECTED WITH FIRE SPRINKLERS. | | | | | | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT TO | | | INSTALL FIRE SPRINKLER PROTECTION UNDER SEPARATE PERMIT | | | AND SHOP DRAWINGS. | | | | | | | | | 3) THERE IS NO INDICATION OF EMERGENCY LIGHTING WITHIN | | | THE COOLER OR TO PROVIDE EMEGENCY GENERATOR CONNECTION. | | | | | | PLEASE PROVIDE DETAILS FOR PROVIDING EMERGENCY LIGHTING | | | THAT IS REQUIRED FOR THIS OCCUPANCY. | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|