Plan Review Notes
Plan Review Notes For Permit 22020621
Permit Number 22020621
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-03-02 16:32:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION OF WHERE IS PROPOSED COOLER
 IS LOCATED WITHIN THE BUILDING.
  
 FOR THE OFFICAIL RECORD AND CONFIRMATION, PLEASE
 PROVIDE A FLOOR PLAN SHOWING WHERE THIS IS PROPOSED.
  
  
  
 2) THERE IS NO INDICATION OF PROVIDING FIRE SPRINKLER
 PROTECTION WITHIN THE COOLER AS REQUIRED PER NFPA 13 IN
 BUILDING PROTECTED WITH FIRE SPRINKLERS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT TO
 INSTALL FIRE SPRINKLER PROTECTION UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
  
 3) THERE IS NO INDICATION OF EMERGENCY LIGHTING WITHIN
 THE COOLER OR TO PROVIDE EMEGENCY GENERATOR CONNECTION.
  
 PLEASE PROVIDE DETAILS FOR PROVIDING EMERGENCY LIGHTING
 THAT IS REQUIRED FOR THIS OCCUPANCY.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  