| Plan Review Notes For Permit 22020573 |
| Permit Number |
22020573 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-25 13:39:52 | FIRE COMMENTS: | | | PROVIDE DETAIL ON HOW TESTING OF ALL PIPING AS WELL AS | | | THE SECONDARY CONTAINMENT PIPING WILL BE CONDUCTED. | | | NFPA 30A 5.4 | | | PROVIDE DETAIL ON THE EMERGENCY SHUTOFF VALVE (ESV) AT | | | THE DISPENSER BASE TO INCLUDE THERMAL ACTIVATION. NFPA | | | 30A 6.3.9 | | | PROVIDE DETAIL ON THE TYPE/RATING OF PORTABLE FIRE | | | EXTINGUISHERS TO BE PROVIDED IN THE DISPENSING AREA. | | | NFPA 30A 9.2.5.2 | | | PROVIDE DETAIL ON WARNING SIGNAGE/WORDING TO BE POSTED | | | IN THE DISPENSING AREA. NFPA 30A 9.2.5.4 | | | |
|