| Plan Review Notes For Permit 22020567 |
| Permit Number |
22020567 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-18 11:23:50 | FIRE PROVISO COMMENTS: | | | SPARE SPRINKLER HEAD BOX SHALL HAVE INVENTORY LABELED | | | ON THE HEAD BOX OF THE QUANTITY AND TYPE OF SPARE | | | SPRINKLERS PROVIDED. NFPA 25 5.4.1.5.6 | | | BRACKET ASSEMBLY FOR THE FLEXIBLE BRAIDED HOSE SHALL BE | | | SECURELY CONNECTED PER THE MANUFACTURERS SPECIFICATION | | | UPON INSPECTION BY THE FIRE PREVENTION BUREAU. | | | |
|