| Plan Review Notes For Permit 22020552 |
| Permit Number |
22020552 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-25 09:58:07 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) CIRCLE OR HI-LITE THE MODEL AND THE WIND PRESSURES | | | OF THE 22" TCC SKYLIGHT LISTED IN THE PRODUCT APPROVAL | | | THAT WILL BE INSTALLED. FBC AMENDMENTS 107.2.1 | | | | | | 2) SPECIFY THE WIND DATA (WINDSPEED, EXPOSURE CATEGORY, | | | MEAN ROOF HEIGHT) ON THE DRAWING. FBC-R301.2.1 | | | | | | 3) SPECIFY THE TYPE OF ROOF (GABLE OR HIP), THE ROOFING | | | MATERIAL, THE ROOF SLOPE AND THE ROOF COMPONENT AND | | | CLADDING PRESSURE ZONE FOR THE SKYLIGHT INSTALLATION. | | | THE DESIGN PRESSURES FOR THE SKYLIGHT ASSEMBLY HAVE TO | | | BE GREATER THAN THE REQUIRED PRESSURES. FBC-R301 | | | | | | 4) PROVIDE A CLEAR AND DETAILED ROOF DIAGRAM THAT SHOWS | | | THE PROPOSED LOCATION OF THE SKYLIGHT. THE ONE THAT WAS | | | SUBMITTED IS NOT CLEAR OR DETAILED ENOUGH. FBC 107.2.1 | | | | | | 5) IF YOU ARE USING A CURB TO RAISE THE SKYLIGHT ABOVE | | | A CONCRETE TILE ROOF, PROVIDE A DETAIL FOR HOW THE CURB | | | FRAMING WILL BE SUPPORTED AND ANCHORED TO THE ROOF. | | | FBC-R301 | | | | | | 6) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | | | | |
|