2022-03-25 09:58:07PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) CIRCLE OR HI-LITE THE MODEL AND THE WIND PRESSURES
 OF THE 22" TCC SKYLIGHT LISTED IN THE PRODUCT APPROVAL
 THAT WILL BE INSTALLED. FBC AMENDMENTS 107.2.1
  
 2) SPECIFY THE WIND DATA (WINDSPEED, EXPOSURE CATEGORY,
 MEAN ROOF HEIGHT) ON THE DRAWING. FBC-R301.2.1
  
 3) SPECIFY THE TYPE OF ROOF (GABLE OR HIP), THE ROOFING
 MATERIAL, THE ROOF SLOPE AND THE ROOF COMPONENT AND
 CLADDING PRESSURE ZONE FOR THE SKYLIGHT INSTALLATION.
 THE DESIGN PRESSURES FOR THE SKYLIGHT ASSEMBLY HAVE TO
 BE GREATER THAN THE REQUIRED PRESSURES. FBC-R301
  
 4) PROVIDE A CLEAR AND DETAILED ROOF DIAGRAM THAT SHOWS
 THE PROPOSED LOCATION OF THE SKYLIGHT. THE ONE THAT WAS
 SUBMITTED IS NOT CLEAR OR DETAILED ENOUGH. FBC 107.2.1
  
 5) IF YOU ARE USING A CURB TO RAISE THE SKYLIGHT ABOVE
 A CONCRETE TILE ROOF, PROVIDE A DETAIL FOR HOW THE CURB
 FRAMING WILL BE SUPPORTED AND ANCHORED TO THE ROOF.
 FBC-R301
  
 6) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  
  