| Plan Review Notes For Permit 22020524 |
| Permit Number |
22020524 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-03-21 17:30:00 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-22020524 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE SHOW THE MAKEUP AIR DUCTWORK AND UNIT. FBC M | | | 508.1 | | | | | | 2) PLEASE SHOW THAT THE MAKE-UP AIR FOR THE HOOD WILL | | | MEET THE REQUIREMENTS FOR TEMPERATURE DIFFERENCE IN FBC | | | M 508.1.1 | | | | | | 3) PLEASE SHOW THAT THE KITCHEN HOOD EXHAUST | | | TERMINATION LOCATION WILL ALSO MEET THE 10 FT | | | REQUIREMENT FROM THE SAME BUILDING OR THE EXCEPTION OF | | | FBC M 506.3.13.3. THE ORIGINAL SHEET M2.1 AND THIS HOOD | | | DRAWING SHEET 3 SHOW THE TERMINATION LOCATION FOR THE | | | HOOD AT DIFFERENT LOCATIONS. | | | | | | 4) PLEASE SUBMIT AN UPDATED AIR BALANCE SCHEDULE TO THE | | | MECHANICAL DRAWINGS FOR PERMIT #20100983. FBC M 508.1.2 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|