| 2022-03-01 07:52:48 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-22020407 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC RES R402 |
| | |
| | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. FBC RES R403.7 |
| | |
| | 3) PLEASE SHOW THE ENERGY CALCULATIONS FOR THE GARAGE |
| | AS THIS IS NOT TYPICALLY A CONDITIONED SPACE. FBC RES |
| | R402.1 |
| | |
| | 4) IT APPEARS THAT THE DRYER EXHAUST FROM BOTH DRYERS |
| | IN THE LAUNDRY AT THE GARAGE ARE RUNNING INTO ONE 4 |
| | INCH DUCT ABOVE THE CEILING AND GOING THRU THE ROOF. |
| | PLEASE SHOW THAT EACH DRYER IS GOING SEPARATELY TO THE |
| | OUTDOORS OR PROVIDE MANUFACTURE?S INSTALLATION |
| | INSTRUCTIONS SHOWING THIS METHOD. FBC RES M1502.3 |
| | |
| | 5) PLEASE PROVIDE A BATH EXHAUST FAN OR SHOW THE |
| | WINDOWS MEET FBC RES R303.3 IN THE 2ND STORY SHOWER |
| | AREAS. |
| | |
| | 6) PLEASE SHOW THE CONDENSATE DRAIN AND TERMINATION |
| | LOCATION. FBC RES M1411.3 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |