| 2022-04-04 12:54:44 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO |
| | CONSTRUCTION TO AVOID CONFLICTS/DELAYS): |
| | 1- PROVIDE LOT DRAINAGE PLAN: NOTE: SHOW EXISTING AND |
| | PROPOSED GRADE ELEVATIONS SHOWING HOW KEEPING WATER |
| | AWAY FROM ADJACENT PROPERTIES. |
| | 2-PROVIDE PRODUCT APPROVALS APPROVED BY ENGINEER OF |
| | RECORD FOR: A)EXTERIOR DOORS. B)WINDOWS. C)WINDOW |
| | MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE). |
| | D)HURRICANE SHUTTERS IF DOORS/WINDOWS DON'T HAVE IMPACT |
| | GLAZING. AND, PROVIDE COMPLETE INSTALLATION SCHEDULE. |
| | SEE CITY SAMPLE. E)METAL ROOF. F)ROOFING UNDERLAYMENT |
| | SPECIFIED ON PLANS FOR METAL ROOFING. G)SLEEPING PORCH |
| | UNDERLAYMENT FOR CERAMIC TILE AS SPECIFIED ON PLANS. |
| | 3- WINDOW FALL PROTECTION SHALL BE PROVIDED ON SECOND |
| | FLOOR WINDOWS WHERE THE TOP OF THE WINDOW SILL OF AN |
| | OPERABLE WINDOW IS LOCATED LESS THAN 24" ABOVE THE |
| | FINISHED FLOOR . SEC. R312.2 FBC RESIDENTIAL. |
| | 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | ALUMINUM TRELLIS CONSTRUCTION. SPECIFY ALL FRAMING |
| | MEMBERS AND CONNECTOR AT EACH END. |
| | 5- REVISE DOORS/WINDOWS DESIGN PRESSURES SHOWN ON THE |
| | EXTERIOR ELEVATIONS TO MATCH DESIGN PRESSURES SPECIFIED |
| | ON SHEET S1. |
| | 6- ENGINEER OF RECORD TO REVISE END ZONE DIMENSION |
| | SPECIFIED UNDER WIND DESIGN CRITERIA ON SHEET S1. THE |
| | MINIMUM DIMENSION IS 4'-0" NOT 3'-0" AS REQUIRED BY |
| | NOTE "A" ON FIGURE R301.2(7) FBC-RESIDENTIAL. |
| | 7- ENGINEER OF RECORD TO PROVIDE SPECIFICATIONS FOR THE |
| | CONCRETE SLAB VAPOR BARRIER AS REQUIRED BY SEC. |
| | R506.2.3 FBC-RESIDENTIAL. |