| 2022-03-21 10:11:18 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected]. |
| | |
| | 1. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED FLAT/LOW SLOPE ROOF |
| | SYSTEM TO BE USED. INCLUDE COVER PAGE, EVALUATION |
| | REPORTS AND INSTALLATION INSTRUCTIONS FOR SYSTEM USED. |
| | ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. PLEASE |
| | NOTE THIS IS A CATEGORY D AREA. |
| | 2. FBC B 107.2.1 FBC EB 706.1 SUBMITTED ROOF |
| | DRAWING/SKETCH LISTS FLAT/LOW ROOF SLOPE AS 0:12; LOW |
| | SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. PROVIDE METHOD |
| | OF PROVIDING POSITIVE DRAINAGE. |
| | 3. SUBMITTED PRODUCT APPROVAL FL27076-R1; MIAMI-DADE |
| | COUNTY NOA 18-0409.06 SELECTED SYSTEM E(1) IS APPROVED |
| | FOR USE AS A BASE SHEET ONLY IN ROOF TILE APPLICATIONS. |
| | PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED ROOF UNDERLAYMENT (CAP |
| | SHEET) TO BE USED. INCLUDE COVER PAGE, EVALUATION |
| | REPORTS AND INSTALLATION INSTRUCTIONS FOR SYSTEM USED. |
| | ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. NOTE: |
| | SYSTEM NUMBER E(4) OF THE SUBMITTED PRODUCT APPROVAL |
| | CAN BE USED IF USING ADHESIVE SET TILE APPLICATION WITH |
| | AN APPROVED ADHESIVE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |