2022-03-28 14:34:402ND REVIEW FBC-2020 MECHANICAL
 PERMIT-22020274
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE APPLICATION FOR THIS PROJECT STATES IT IS FOR A
 NEW HVAC. THE ASHRAE DOCUMENT IS FOR A RTU REPLACEMENT.
 THERE IS NOTHING OTHER THAN A 1 PAGE FORM WITH THIS
 ASHRAE DOCUMENT. PLEASE HELP THIS REVIEWER UNDERSTAND
 THE NEED FOR AN ADDITIONAL MECHANICAL SYSTEM. THE
 APPLICATION STATES THIS NEW SYSTEM ADDITION IS DUE TO
 INCREASE DEMAND, WHAT IS THIS INCREASED DEMAND? PLEASE
 PROVIDE THE COMPLETE MECHANICAL SYSTEM EQUIPMENT SIZING
 CALCULATIONS FOR THIS TENANT SPACE TO SHOW WHY ANOTHER
 4 TON SYSTEM IS REQUIRED. FMC 312.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  