2022-06-21 09:49:02ELECTRIC REVIEW FAILED
 1) IT APPEARS THE AIR CONDITIONING LOAD WAS OMMITTED
 FROM THE LOAD CALCULATION. PLEASE CORRECT AS
 APPLICABLE. NEC 215.5
 2) IT APPEARS TH 2/0 CONDUCTORS FEEDING THE INTERIOR
 PANEL ARE INCORRECTLY SIZED PER NEC 310.15 (B( (7)(2)
 CONDUCTORS CAN BE DERATED TO 83% ONLY IF IF SERVES THE
 ENTITE LOAD OF THE DWELLING. PLEASE CORRECT AS
 APPLICABLE
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  