| Date |
Text |
| 2022-02-08 11:45:59 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1 PLEASE CLARITY ROOFING SYSTEM USED. |
| | THE TWO SYSTEMS PROPOSED ARE NOT APPROVED FOR USE WITH |
| | EACH OTHER. |
| | 2. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED FLAT ROOF SYSTEM TO BE |
| | USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND |
| | INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | SUBMITTED PRODUCT APPROVAL FL11288-R19 IS NOT AN |
| | APPROVED FLAT ROOF SYSTEM, IT IS APPROVED FOR USE AS AN |
| | UNDERLAYMENT. (IF APPLICABLE). |
| | 3. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| | FL15027-R7 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| | ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-8 TO |
| | INCLUDE LIMITATIONS PAGE(S), TECHNICAL BULLENTIN-110 |
| | PAGES 1-2. THE EVALUATION REPORTS & TECHNICAL |
| | BULLENTIN-110 CAN BE PRINTED FROM THE SUMMARY OF |
| | PRODUCTS LOCATED AT THE BOTTOM OF THE COVER PAGE. (IF |
| | APPLICABLE) |
| | 4. FBC B 107.2.1 PROVIDE CERTIFICATION THAT |
| | REQUIREMENTS OF 4.4.1 OF THE EVALUATION REPORT PAGE #4 |
| | OF PRODUCT APPROVAL FL15027.2 HAS BEEN MET & IDENTIFY |
| | SYSTEM USED FROM TABLE 1, TABLE 1A OR TABLE 2 PAGES |
| | 4-5. (IF APPLICABLE) |
| | 5. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| | DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S). FLAT/LOW |
| | SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |