| 2022-08-24 09:46:32 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | | | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | | APPROVAL FL16709-R10 SELECTED OPTION FOR SYSTEM NO W-5 | | | EXPOSURE (D); ENCLOSURE (ENCLOSED); ROOF HEIGHT (15 H < | | | 20); ULTIMATE WIND SPEED (180). ZONE 3 IS MARKED ?N/A? | | | WHICH INDICATES SYSTEM IS ?NOT APPLICABLE? TO ZONE1 | | | PRIME DESIGN PRESSURE REQUIREMENTS AND CANNOT BE USED. | | | PLEASE PROVIDE 2020 CODE VERSION PRODUCT APPROVAL/NOA | | | THAT MEETS OR EXCEEDS DESIGN PRESSURE REQUIREMENTS FOR | | | EXPOSURE D AREAS. SIGNED AND SEALED NAILING | | | CALCULATIONS MAY BE REQUIRED. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|