| 2022-02-24 11:21:37 | ELECTRIC REVIEW FAILED |
| | 1)ELECTRIC SERVICE RISER DETAILS 4/0 AL CONDUCTORS FOR |
| | 200-AMP PANEL AND 2/0 AL CONDUCTORS TO A 150-AMP PANEL. |
| | NEC 310.15.(B)(7)(2) STATES FEEDER CONDUCTORS SERVING |
| | THE ENTIRE LOAD BE ABLE TO BE REDUCED TO 83% AMPACITY. |
| | THE FEEDER CONDUCTORS DETAILED DO NOT CARRY THE ENTIRE |
| | LOAD OF THE SERVICE THEREFORE MUST BE SIZED TO SERVE |
| | THE LOAD NEC 215.29A)(1)(B) THE MINIMUM FEEDER |
| | CONDUCTOR SIZE SHALL HAVE AN ALLOWABLE AMPACITY NOT |
| | LESS THAN THE MAXIMUM LOAD TO BE SERVED AFTER THE |
| | APPLICATION OF ANY ADJUSTMENT OR CORRECTION FACTORS. |
| | 2) DRAWINGS DO NOT DETAIL ELECTRIC PANEL OR POOL AND |
| | SPA EQUIPMENT LOCATIONS. PLEASE ALL ELECTRIC SUB PANEL |
| | LOCATIONS AND CONDUCTOR SIZE SERVING LOADS. FBC 107.2 |
| | 3) LOAD CALCULATION DOES NOT DETAIL AND POOL AND SPA |
| | LOADS. PLEASE SHOW ALL LOADS WHETHER THEY ARE EXISTING |
| | OR NEW. NEC 215.5 FBC 107.3 |
| | 4) PLEASE DETAIL CIRCUITS TO BE GFI OR ARC FAULT |
| | PROTECTED. A NOTE WILL SUFFICE. NEC 210.8 NEC 210.12 |
| | AND NEC 406.4 |
| | 5) IT APPEARS THE RECEPTACLE SPACING AT KITCHEN COUNTER |
| | AREAS DO NOT MEET THE REQUIREMENTS AS PER NEC 210.52. |
| | PLEASE CORRECT AS NECESSARY |
| | 6)PLEASE DETAIL SMOKE AND CARBON MONOXIDE DETECTORS AS |
| | REQUIRED PER FBC R315.1 |
| | 7) PLEASE DETAIL RECEPTACLES TO BE TAMPER RESISTANT AS |
| | PER NEC 406.12 AND NEC 406.4(D)(5). A NOTE WILL SUFFICE |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |