| Date |
Text |
| 2022-08-02 10:38:43 | 3RD REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22020213 |
| | 8/2/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST AND 2ND REVIEW ARE LISTED BELOW WITH ADDITIONAL |
| | NOTES. PLEASE REVIEW THE COMMENTS AND IF YOU QUESTIONS |
| | PLEASE CONTACT ME FOR ASSISTANCE. |
| | |
| | 5) FAILED. P102: PROVIDE A MASTER THERMOSTATIC MIXING |
| | VALVE AT THE WATER HEATER OR INDIVIDUAL MIXING VALVES |
| | AT ALL HOT WATER SUPPLIED FIXTURES- SEC. 607.1.1 FBC P. |
| | HOT WATER AT A MINIMUM TEMPERATURE 0F 110 DEGREES F IS |
| | REQUIRED AT THE LAB SINK P-3E AND FROM ONE BOWL OF LAB |
| | SINK P-9 PER SEC. 607.1 FBC P. PLEASE CORRECT THE NOTES |
| | IN THE PLUMBING FIXTURE SCHEDULE ON P601 AND PROVIDE A |
| | MEANS OF LIMITING THE HOT WATER TEMPERATURE DELIVERY AT |
| | THE SINKS- SEC. 607.1.1. ACKNOWLEDGED THAT THE EYE WASH |
| | IN IN COMPLIANCE. THE MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION GUIDELINES WILL BE DEFERRED SUBMITTALS. |
| | |
| | 6) FAILED. P102: NOTE #3 FOR THE WATER HEATER IS BEING |
| | USED TO IDENTIFY ANOTHER UNKNOWN PIECE OF EQUIPMENT IN |
| | THE RM 121. PLEASE CORRECT THE NOTE AND ADD THE |
| | EQUIPMENT TO THE SCHEDULE- SEC. 107.2.1 WPB. THE |
| | EQUIPMENT PLAN AND SCHEDULE INDICATE A WATER SOLENOID |
| | VALVE AT NOTE #3. PLEASE PROVIDE A DIFFERENT NUMBERED |
| | NOTE AND A DETAIL FOR THE ASSEMBLY ON SHEET P501. |
| | |
| | NEW COMMENT |
| | |
| | 1) REFER TO SEC. 107.3.4.1 WPB AND PROVIDE A LIST OF |
| | DEFERRED SUBMITTALS ON TJHE PLAN INCLUDING BUT NOT |
| | LIMITED TO: |
| | EYEWASH STATION |
| | PLASTER TRAPS |
| | WATER HEATER |
| | WASHING MACHINE |
| | LINT INTERCEPTOR |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | |