2022-08-02 10:38:433RD REVIEW FBC-2020 PLUMBING
 PERMIT- 22020213
 8/2/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST AND 2ND REVIEW ARE LISTED BELOW WITH ADDITIONAL
 NOTES. PLEASE REVIEW THE COMMENTS AND IF YOU QUESTIONS
 PLEASE CONTACT ME FOR ASSISTANCE.
  
 5) FAILED. P102: PROVIDE A MASTER THERMOSTATIC MIXING
 VALVE AT THE WATER HEATER OR INDIVIDUAL MIXING VALVES
 AT ALL HOT WATER SUPPLIED FIXTURES- SEC. 607.1.1 FBC P.
 HOT WATER AT A MINIMUM TEMPERATURE 0F 110 DEGREES F IS
 REQUIRED AT THE LAB SINK P-3E AND FROM ONE BOWL OF LAB
 SINK P-9 PER SEC. 607.1 FBC P. PLEASE CORRECT THE NOTES
 IN THE PLUMBING FIXTURE SCHEDULE ON P601 AND PROVIDE A
 MEANS OF LIMITING THE HOT WATER TEMPERATURE DELIVERY AT
 THE SINKS- SEC. 607.1.1. ACKNOWLEDGED THAT THE EYE WASH
 IN IN COMPLIANCE. THE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION GUIDELINES WILL BE DEFERRED SUBMITTALS.
  
 6) FAILED. P102: NOTE #3 FOR THE WATER HEATER IS BEING
 USED TO IDENTIFY ANOTHER UNKNOWN PIECE OF EQUIPMENT IN
 THE RM 121. PLEASE CORRECT THE NOTE AND ADD THE
 EQUIPMENT TO THE SCHEDULE- SEC. 107.2.1 WPB. THE
 EQUIPMENT PLAN AND SCHEDULE INDICATE A WATER SOLENOID
 VALVE AT NOTE #3. PLEASE PROVIDE A DIFFERENT NUMBERED
 NOTE AND A DETAIL FOR THE ASSEMBLY ON SHEET P501.
  
 NEW COMMENT
  
 1) REFER TO SEC. 107.3.4.1 WPB AND PROVIDE A LIST OF
 DEFERRED SUBMITTALS ON TJHE PLAN INCLUDING BUT NOT
 LIMITED TO:
 EYEWASH STATION
 PLASTER TRAPS
 WATER HEATER
 WASHING MACHINE
 LINT INTERCEPTOR
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  