Plan Review Notes
Plan Review Notes For Permit 22020213
Permit Number 22020213
Review Stop MEDGAS
Sequence Number 3
Notes
Date Text
2022-08-02 12:15:453RD REVIEW FBC-2020 PLUMBING/ MED-GAS
 PERMIT- 22020213
 8/2/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 NFPA-99-2018
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST AND 2ND ARE LISTED BELOW WITH ADDITIONAL NOTES.
 PLEASE REVIEW THE COMMENTS BELOW AND NOTE THAT
 INSTALLATION OF THE MED GAS SYSTEM MAY BE DONE UNDER A
 SEPARATE PERMIT.
  
 2) FAILED: LABEL THE GAS CYLINDERS IN DETAIL 10/P501 AS
 EITHER O2 OR N2O. INDICATE THE CU. FT. CAPACITIES OF
 THE CYLINDERS AND SUBMIT MANUFACTURER'S SPECIFICATIONS-
 SECS. 15.3.3.1.1 & 5.1.3.1.1 NFPA 99. THE CYLINDERS
 SHALL BE DESIGNED, FABRICATED, TESTED AND STAMPED IN
 ACCORDANCE WITH REGULATIONS OF DOT, TRANSPORT CANADA
 (TC) TRANSPORTATION OF DANGEROUS GOODS REGULATIONS, OR
 THE ASME BOILER AND PRESSURE VESSEL CODE. REQUESTED
 TANK SPECS NOT PROVIDED.
  
 8) FAILED.: INDICATE HOW MAKEUP AIR FOR THE EXHAUST
 WILL BE PROVIDED- SECS. 15.3.2.1, 5.1.3.3.3.1 &
 9.3.6.5.3.7 NFPA 99. THE M101 PLAN DOES NOT
 SPECIFICALLY SHOW HOW MAKEUP AIR FOR THE EXHAUST IS
 BEING PROVIDED. PLEASE REFER TO SEC. 9.3.6.5.3.7 ITEMS
 1, 2, & 3) NFPA 99- A NON-COMBUSTIBLE DUCT CAN BE USED
 TO TRANSFER AIR FROM ADJACENT SPACES OF FROM THE
 OUTSIDE. PLEASE NOTE THE ARCHITECTURAL PLANS INDICATE
 THE ROOM AND DOOR ARE FIRE-RATED AND SMOKE SEALED. 8A)
 SHEET M101 SHOWS AN IN-LINE EXHAUST FAN INSTALLED IN
 THE 2- HR. FIRE-WRAPPED DUCT, HOWEVER THE FIRE-RATED
 ENCLOSURE OR SHAFT IS REQUIRED TO BE CONTINUOUS FROM
 THE GAS ROOM TO THE EXTERIOR OF THE BUILDING- SECS.
 502.9.1 & 510.7.3 FBC M. PLEASE CLARIFY IF THE FAN WILL
 BE HOUSED IN A 2-HR FIRE-RATED ENCLOSURE WITH SERVICE
 ACCESS, OR WILL SOME OTHER MEANS BE PROVIDED TO
 MAINTAIN THE CONTINUITY OF THE SHAFT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER