| Date |
Text |
| 2022-06-07 13:32:41 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22020213 |
| | 6/7/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES. |
| | PLEASE NOTE THAT THE COMMENT RESPONSES FROM THE |
| | ARCHITECT WERE INCOMPLETE AND DID NOT ADDRESS ALL OF |
| | THE COMMENTS. |
| | |
| | 1) FAILED. SHEET A501 DETAIL 2C: THE CENTERLINES OF THE |
| | TOILET PAPER DISPENSERS SHALL BE 7-INCHES MINIMUM AND |
| | 9-INCHES MAXIMUM MEASURED FROM THE FRONTS OF THE WATER |
| | CLOSETS- SEC. AND FIG. 604.7 FBC ACC. CENTERLINE OF THE |
| | DISPENSER NOT THE ROLL AS THE DETAIL SHOWS. NEW |
| | COMMENT: ON SHEET A501 PLEASE CHANGE THE 54-INCH CLEAR |
| | FLOOR SPACE DIMESNION FOR THE WATER CLOSETS TO |
| | 56-INCHES AS REQUIRED BY SEC. 604.3.1 FBC ACC. THE PLAN |
| | ALSO APPEARS TO SHOW A FIXED PIECE OF FURNITURE |
| | OBSTRUCTING THE CLEARANCE- SEC. 604.3.2. |
| | |
| | 4) FAILED. A101 & A503: IN ACCORDANCE WITH SEC. 212.3 |
| | FBC ACC- WHERE SINKS ARE PROVIDED, AT LEAST 5 PERCENT, |
| | BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED IN EACH |
| | ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606. PLEASE |
| | SHOW THE CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR |
| | THE ACCESSIBLE SINKS INCLUDING THE BREAKROOM, WORK AND |
| | EXAM SINKS- SEC. 606.2 FBC ACC. PROVIDE ELEVATION |
| | DETAILS FOR THE SINKS. MINIMUM OF ONE EXAM ROOM SINK |
| | SHALL BE ACCESSIBILE. PLEASE NOTE THAT THE EXAM ROOM |
| | SINKS ARE MISLABELED AS P-3A IN THE SANITARY RISER |
| | DRAWING. PLEASE PROVIDE P-3C LABELS AT THE SINKS. |
| | |
| | 5) FAILED. P102: PROVIDE A MASTER THERMOSTATIC MIXING |
| | VALVE AT THE WATER HEATER OR INDIVIDUAL MIXING VALVES |
| | AT ALL HOT WATER SUPPLIED FIXTURES- SEC. 607.1.1 FBC P. |
| | THE RESPONSE LETTER CALLS OUT ASSE 1070 MIXING VALVES |
| | FOR TEMPERED DELIIVERY FROM THE LAVATORIES, HOWEVER A |
| | MEANS OF LIMITING THE HOT WATER TEMPERATURE DELIVERY AT |
| | THE OTHER SINKS IN THE FACILITY IS REQUIRED AND CANNOT |
| | BE THE THERMOSTAT EQUIPPED WITH THE WATER HEATER. |
| | |
| | 6) FAILED. P102: NOTE #3 FOR THE WATER HEATER IS BEING |
| | USED TO IDENTIFY ANOTHER UNKNOWN PIECE OF EQUIPMENT IN |
| | THE RM 121. PLEASE CORRECT THE NOTE AND ADD THE |
| | EQUIPMENT TO THE SCHEDULE- SEC. 107.2.1 WPB. THE |
| | EQUIPMENT PLAN AND SCHEDULE INDICATE A SOLENOID VALVE |
| | AT NOTE #3. PLEASE PROVIDE A DIFFERENT NUMBERED NOTE |
| | AND A DETAIL FOR THE ASSEMBLY ON SHEET P501. |
| | |
| | 7) FAILED. P101, P201, P501, P601: DETAILS 5/P501 & |
| | 6/P501 APPEAR TO BE IN CONFLICT CONCERNING VACUUM PUMP |
| | DRAINAGE. PLEASE NOTE AN INDIRECT WASTE RECEPTOR IS |
| | REQUIRED PER SEC. 802.1.5 FBC P. PLEASE REVISE THE |
| | SANITARY DRAINAGE LAYOUT PLAN AND ISOMETRIC DRAWING TO |
| | SHOW THE FLOOR DRAIN, THE VENTING, AND TRAP SEAL |
| | PROTECTION- SEC. 107.3.5.1.3 WPB & SEC.1002.4.1 FBC P. |
| | REMOVE ALL NON-COMPLIANT OR INCONSISTENT DETAILS AND |
| | PROVIDE AN VACUUM INTAKE/EXHAUST DIAGRAM PER DETAIL |
| | 7/P501. SHOW THE TYPE AND SIZE OF PIPING, PIPING RUNS, |
| | AND TERMINATION LOCATIONS- SEC. 107.2.1 WPB & SEC. |
| | 1202.1 FBC P. A) SUBMIT MANUFACTURER'S SPECS FOR THE |
| | VACUUM, COMPRESSOR AND ALL ASSOCIATED PIPING AND |
| | APPURTENANCES- SEC. 107.2.1 WPB & SEC.1202.1 FBC P, AND |
| | SECS. 5.1.3.6.3.4- 5.1.3.6.3.11 & 5.1.3.7.2 NFPA 99. |
| | 2ND REQUEST FOR VACUUM AND COMPRESSOR INTAKE AND |
| | EXHAUST DIAGRAMS PLEASE SHOW ON THE PLANS THE PIPING |
| | RUNS, TYPES AND SIZES OF PIPES, AND TERMINATION |
| | LOCATIONS. PLEASE NOTE THAT THE VACUUM MUST BE EQUIPPED |
| | WITH A HEAT EXCHANGER IF SCHEDULE 40 PVC EXHAUST PIPING |
| | IS TO BE USED. |
| | |
| | 8) FAILED. NO RESPONSE PROVIDED. P101: CLARIFY IF THE |
| | COMPRESSOR WILL PRODUCE CONDENSATE AND PROVIDE A |
| | CONDENSATE DISPOSAL PLAN IF APPLICABLE- SECS. 314.2 & |
| | 314.2.1 FBC P. THE SUBMITTED SPECIFICATIONS INDICATE |
| | THE COMPRESSOR REQUIRES A MEANS OF DISPOSING CONDENSATE |
| | FROM THE REMOTE AIR INTAKE AND MOSITURE FROM THE |
| | MEMBRANE DRYER- PAGE 10. A WASTE RECEPTOR SHALL BE |
| | PROVIDED IN THE EQUIPMENT ROOM- SEC. 802.1 FBC P. |
| | |
| | 9) FAILED. NO RESPONSE PROVIDED. P102: PROVIDE A WATER |
| | RISER DRAWING- SEC. 107.3.5.1.3 WPB. |
| | |
| | 12) FAILED. NO RESPONSE PROVIDED.P101 & P601: PLEASE |
| | PLACE NOTES ON THE PLAN TO IDENTIFY THE LOCATIONS OF |
| | THE WASHING MACHINE AND REQUIRED LINT TRAP- SECS. 406.1 |
| | & 1003.6 FBC P. A) PROVIDE AN ENLARGED DETAIL SHOWING |
| | THE WATER SUPPLY PIPING CONNECTIONS, WATER HAMMER |
| | ARRESTOR, AND THE DRAINAGE AND VENT PIPE CONNECTIONS |
| | FOR THE INTERCEPTOR. SUBMIT MANUFACTURER'S SPECS FOR |
| | THE WASHING MACHINE AND LINT TRAP. |
| | |
| | 13) FAILED. NO REPONSE PROVIDED. P102 NOTE 6: INDICATE |
| | THE RPZ BACKFLOW PREVENTER INSTALLATION WILL BE UNDER |
| | SEPARATE PERMIT- SEC. 105.1 FBC P. PLEASE NOTE THE |
| | FOLLOWING CONCERNING THE BACKFLOW PREVENTER FOR THE |
| | POTABLE WATER SERVICE (SHEET C-111) AND FOR THE WATER |
| | SUPPLY TO THE VACUUM SHALL BE UNDER SEPARATE PERMITS. |
| | DUE TO A CHANGE IN PROCESS, THE BACKFLOW PERMITS ARE |
| | REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE |
| | PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN |
| | APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE |
| | A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| | APPLICATION TO [email protected] . YOU WILL |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| | YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER |
| | YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL |
| | AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | 14) FAILED. NO RESPONSES PROVIDED. PLEASE NOTE THE |
| | COPIED SECTIONS BELOW DERIVED FROM THE CITY OF WEST |
| | PALM BEACH CODE OF ORDINANCES PERTAINING TO DENTAL AND |
| | MEDICAL FACILITY WASTE DISPOSAL. NOTE IN PARTICULAR |
| | SEC.90-126(I1) CONCERNING THE VACUUM SYSTEM. PLEASE |
| | NOTE THAT MANUFACTURER'S SPECIFICATIONS FOR THE AMALGAM |
| | SEPARATOR WERE NOT SUBMITTED FOR REVIEW. |
| | AN ISO 11143 OR ANSI/ADA STANDARD NO. 108 CERTIFIED |
| | AMALGAM SEPARATOR OR EQUIVALENT DEVICE SHALL BE |
| | INSTALLED FOR EACH DENTAL VACUUM SUCTION SYSTEM. THE |
| | INSTALLED DEVICE MUST BE ISO 11143 OR ANSI/ADA STANDARD |
| | NO. 108 CERTIFIED AS CAPABLE OF REMOVING A MINIMUM OF |
| | 95 PERCENT OF AMALGAM. THE AMALGAM SEPARATOR SYSTEM |
| | SHALL BE CERTIFIED AT FLOW RATES COMPARABLE TO THE FLOW |
| | RATE OF THE ACTUAL VACUUM SUCTION SYSTEM OPERATION. |
| | NEITHER THE SEPARATOR DEVICE NOR THE RELATED PLUMBING |
| | SHALL INCLUDE AN AUTOMATIC FLOW BYPASS. FOR FACILITIES |
| | THAT REQUIRE AN AMALGAM SEPARATOR THAT EXCEEDS THE |
| | PRACTICAL CAPACITY OF ISO 11143 TEST METHODOLOGY, A |
| | NON-CERTIFIED SEPARATOR WILL BE ACCEPTED, PROVIDED THAT |
| | SMALLER UNITS FROM THE SAME MANUFACTURER AND OF THE |
| | SAME TECHNOLOGY ARE ISO-CERTIFIED. |
| | |
| | CONCERNING THE ITEMS BELOW PLEASE ACKNOWLEDGE RECEIPT |
| | AND REVIEW OF THE ORDINANCE. |
| | |
| | SECS. 90-126 (H-M) |
| | ALL OWNERS AND OPERATORS OF DENTAL FACILITIES THAT |
| | REMOVE OR PLACE AMALGAM FILLINGS SHALL COMPLY WITH THE |
| | FOLLOWING REPORTING AND WASTE MANAGEMENT PRACTICES: |
| | (1) |
| | FOR EXISTING SOURCES, A ONE-TIME COMPLIANCE REPORT IS |
| | DUE NO LATER THAN 90 DAYS AFTER TRANSFER OF OWNERSHIP. |
| | (2) |
| | FOR NEW SOURCES, A ONE-TIME COMPLIANCE REPORT IS DUE |
| | WITHIN 90 DAYS OF THE START OF DISCHARGE TO THE SEWER |
| | COLLECTION SYSTEM. |
| | (3) |
| | NO PERSON SHALL RINSE CHAIRSIDE TRAPS, VACUUM SCREENS, |
| | OR AMALGAM SEPARATORS EQUIPMENT IN A SINK OR OTHER |
| | CONNECTION TO THE SANITARY SEWER. |
| | (4) |
| | OWNERS AND OPERATORS OF DENTAL FACILITIES SHALL ENSURE |
| | THAT ALL STAFF MEMBERS WHO HANDLE AMALGAM WASTE ARE |
| | TRAINED IN PROPER HANDLING, MANAGEMENT AND DISPOSAL OF |
| | MERCURY-CONTAINING MATERIAL AND FIXER-CONTAINING |
| | SOLUTIONS AND SHALL MAINTAIN TRAINING RECORDS THAT |
| | SHALL BE AVAILABLE FOR INSPECTION BY THE CITY |
| | INDUSTRIAL PRETREATMENT DIVISION DURING NORMAL BUSINESS |
| | HOURS. |
| | (5) |
| | AMALGAM WASTE SHALL BE STORED AND MANAGED IN ACCORDANCE |
| | WITH THE INSTRUCTIONS OF THE RECYCLER OR HAULER OF SUCH |
| | MATERIALS. |
| | (6) |
| | BLEACH AND OTHER CHLORINE-CONTAINING DISINFECTANTS |
| | SHALL NOT BE USED TO DISINFECT THE VACUUM LINE SYSTEM. |
| | (7) |
| | THE USE OF BULK MERCURY IS PROHIBITED. ONLY |
| | PRE-CAPSULATED DENTAL AMALGAM IS PERMITTED. |
| | (I) |
| | ALL OWNERS AND OPERATORS OF DENTAL VACUUM SUCTION |
| | SYSTEMS, EXCEPT AS SET FORTH IN SUBSECTIONS (J) AND (K) |
| | OF THIS SECTION, SHALL COMPLY WITH THE FOLLOWING: |
| | (1) |
| | AN ISO 11143 OR ANSI/ADA STANDARD NO. 108 CERTIFIED |
| | AMALGAM SEPARATOR OR EQUIVALENT DEVICE SHALL BE |
| | INSTALLED FOR EACH DENTAL VACUUM SUCTION SYSTEM. THE |
| | INSTALLED DEVICE MUST BE ISO 11143 OR ANSI/ADA STANDARD |
| | NO. 108 CERTIFIED AS CAPABLE OF REMOVING A MINIMUM OF |
| | 95 PERCENT OF AMALGAM. THE AMALGAM SEPARATOR SYSTEM |
| | SHALL BE CERTIFIED AT FLOW RATES COMPARABLE TO THE FLOW |
| | RATE OF THE ACTUAL VACUUM SUCTION SYSTEM OPERATION. |
| | NEITHER THE SEPARATOR DEVICE NOR THE RELATED PLUMBING |
| | SHALL INCLUDE AN AUTOMATIC FLOW BYPASS. FOR FACILITIES |
| | THAT REQUIRE AN AMALGAM SEPARATOR THAT EXCEEDS THE |
| | PRACTICAL CAPACITY OF ISO 11143 TEST METHODOLOGY, A |
| | NON-CERTIFIED SEPARATOR WILL BE ACCEPTED, PROVIDED THAT |
| | SMALLER UNITS FROM THE SAME MANUFACTURER AND OF THE |
| | SAME TECHNOLOGY ARE ISO-CERTIFIED. |
| | (2) |
| | PROOF OF CERTIFICATION AND INSTALLATION RECORDS SHALL |
| | BE SUBMITTED TO THE CITY INDUSTRIAL PRETREATMENT |
| | DIVISION WITHIN 30 DAYS OF INSTALLATION. |
| | (3) |
| | AMALGAM SEPARATORS SHALL BE MAINTAINED IN ACCORDANCE |
| | WITH MANUFACTURER RECOMMENDATIONS. INSTALLATION, |
| | CERTIFICATION, AND MAINTENANCE RECORDS SHALL BE |
| | AVAILABLE FOR IMMEDIATE INSPECTION UPON REQUEST |
| | THEREFOR BY THE CITY INDUSTRIAL PRETREATMENT DIVISION |
| | DESIGNEE DURING NORMAL BUSINESS HOURS. RECORDS SHALL BE |
| | MAINTAINED FOR A MINIMUM OF THREE YEARS. |
| | (J) |
| | FACILITIES WITH VACUUM SUCTION SYSTEMS THAT MEET ALL |
| | THE FOLLOWING CONDITIONS MAY APPLY TO THE CITY |
| | INDUSTRIAL PRETREATMENT DIVISION FOR AN EXEMPTION TO |
| | THE REQUIREMENTS OF SUBSECTION (I) OF THIS SECTION: |
| | (1) |
| | THE SYSTEM IS A DRY VACUUM PUMP SYSTEM WITH AN |
| | AIR-WATER SEPARATOR. |
| | (2) |
| | THE SEDIMENTATION TANK IS NON-BOTTOM DRAINING, WITH THE |
| | DRAIN ABOVE THE ANTICIPATED MAXIMUM LEVEL OF |
| | ACCUMULATED SLUDGE. |
| | (3) |
| | EVIDENCE OF REGULAR PUMP OUTS BY A LICENSED HAULER (A |
| | MINIMUM OF ONCE A YEAR, OR MORE OFTEN IF EITHER |
| | DIRECTED BY THE MANUFACTURER OR NECESSARY TO KEEP |
| | SOLIDS FROM EXITING THROUGH THE DRAIN) IS MAINTAINED |
| | AND OPEN TO INSPECTION BY CITY STAFF DURING NORMAL |
| | BUSINESS HOURS. |
| | (4) |
| | THE SYSTEM HAS NO DIRECT DISCHARGE PIPE TO THE SEWER ON |
| | THE BOTTOM OF THE SEDIMENTATION TANK. |
| | AN OWNER OR OPERATOR WHOSE FACILITY MEETS CONDITIONS |
| | (1) THROUGH (4) MAY APPLY FOR THIS EXEMPTION BY WRITTEN |
| | LETTER TO THE CITY INDUSTRIAL PRETREATMENT DIVISION. AN |
| | IPP DESIGNEE WILL REVIEW THE SYSTEM AND, IF THE |
| | EXEMPTION IS APPROVED, SHALL PROVIDE A WRITTEN LETTER |
| | OF EXEMPTION. |
| | AN EXEMPTION OBTAINED PURSUANT TO THIS SUBSECTION (J) |
| | SHALL EXPIRE UPON INSTALLATION OF A NEW VACUUM SYSTEM. |
| | UPON EXPIRATION OF THE EXEMPTION, THE FACILITY SHALL |
| | COMPLY WITH SUBSECTION (I) OF THIS SECTION BEFORE |
| | COMMENCING FURTHER OPERATION. |
| | (K) |
| | DENTAL DISCHARGERS THAT EXCLUSIVELY PRACTICE ONE OR |
| | MORE OF THE FOLLOWING SPECIALTIES ARE NOT SUBJECT TO |
| | THE REQUIREMENTS OF THIS SECTION: (1) ORTHODONTICS; (2) |
| | PERIODONTICS; (3) ORAL AND MAXILLOFACIAL SURGERY; (4) |
| | RADIOLOGY; (5) ORAL PATHOLOGY OR ORAL MEDICINE; (6) |
| | ENDODONTISTRY AND PROSTHODONTISTRY. |
| | (L) |
| | DENTAL PRACTICES THAT DO NOT PLACE DENTAL AMALGAM, AND |
| | DO NOT REMOVE AMALGAM EXCEPT IN LIMITED EMERGENCY OR |
| | UNPLANNED, UNANTICIPATED CIRCUMSTANCES, ARE EXEMPT FROM |
| | THE REQUIREMENTS OF THIS PART, PROVIDED THE DENTAL |
| | PRACTICE: |
| | (1) |
| | SUBMITS THE FOLLOWING STATEMENT TO THE CITY INDUSTRIAL |
| | PRETREATMENT DIVISION, SIGNED BY A RESPONSIBLE |
| | CORPORATE OFFICER, GENERAL PARTNER, PROPRIETOR, OR A |
| | DULY AUTHORIZED REPRESENTATIVE BY THE APPLICABLE |
| | COMPLIANCE DEADLINE IDENTIFIED IN SECTION 90-126(H)(1) |
| | AND 90-126(H)(2): |
| | "THIS FACILITY IS A DENTAL DISCHARGER SUBJECT TO THIS |
| | RULE AND DOES NOT PLACE OR REMOVE DENTAL AMALGAM EXCEPT |
| | IN LIMITED EMERGENCY OR UNPLANNED, UNANTICIPATED |
| | CIRCUMSTANCES. I AM A RESPONSIBLE CORPORATE OFFICER, A |
| | GENERAL PARTNER OR PROPRIETOR (IF THE FACILITY IS A |
| | PARTNERSHIP OR SOLE PROPRIETORSHIP), OR A DULY |
| | AUTHORIZED REPRESENTATIVE IN ACCORDANCE WITH THE |
| | REQUIREMENTS OF 403.12(L) OF THE ABOVE NAMED DENTAL |
| | FACILITY, AND CERTIFY UNDER PENALTY OF LAW THAT THIS |
| | DOCUMENT AND ALL ATTACHMENTS WERE PREPARED UNDER MY |
| | DIRECTION OR SUPERVISION IN ACCORDANCE WITH A SYSTEM |
| | DESIGNED TO ASSURE THAT QUALIFIED PERSONNEL PROPERLY |
| | GATHER AND EVALUATE THE INFORMATION SUBMITTED. BASED ON |
| | MY INQUIRY OF THE PERSON OR PERSONS WHO MANAGE THE |
| | SYSTEM, OR THOSE PERSONS DIRECTLY RESPONSIBLE FOR |
| | GATHERING THE INFORMATION, THE INFORMATION SUBMITTED |
| | IS, TO THE BEST OF MY KNOWLEDGE AND BELIEF, TRUE, |
| | ACCURATE, AND COMPLETE. I AM AWARE THAT THERE ARE |
| | SIGNIFICANT PENALTIES FOR SUBMITTING FALSE INFORMATION, |
| | INCLUDING THE POSSIBILITY OF FINE AND IMPRISONMENT FOR |
| | KNOWING VIOLATIONS." |
| | (2) |
| | REMOVES DENTAL AMALGAM FOR LIMITED EMERGENCY OR |
| | UNPLANNED, UNANTICIPATED CIRCUMSTANCES, LESS THAN TEN |
| | TIMES PER YEAR OR NO MORE THAN TEN PERCENT OF DENTAL |
| | PROCEDURES; AND |
| | (3) |
| | THE DENTAL PRACTICE NOTIFIES THE CITY OF ANY CHANGES |
| | AFFECTING THE APPLICABILITY OF THIS CERTIFICATION. |
| | (4) |
| | DISPOSAL OF HAULED WASTE FROM DENTAL FACILITIES TO THE |
| | SANITARY SEWER IS PROHIBITED IN ACCORDANCE WITH SECTION |
| | 90-126(B)(8). |
| | (M) |
| | CONTROL OF DISCHARGE. IF ANY WASTES OR WASTEWATERS ARE |
| | DISCHARGED, OR ARE PROPOSED TO BE DISCHARGED, TO THE |
| | WWF WHICH CONTAIN THE SUBSTANCES OR POSSESS THE |
| | CHARACTERISTICS ENUMERATED IN THIS SECTION AS |
| | PROHIBITED BY THIS ARTICLE, DO NOT MEET APPLICABLE |
| | PRETREATMENT STANDARDS AND REQUIREMENTS, AND/OR WHICH |
| | MAY HAVE A DELETERIOUS EFFECT UPON THE WWF, ITS |
| | PROCESSES, EQUIPMENT, OR RECEIVING WATERS, OR WHICH |
| | OTHERWISE CREATE A HAZARD TO LIFE OR CONSTITUTE A |
| | PUBLIC NUISANCE, THE CITY MAY: |
| | (1) |
| | REJECT THE WASTES OR DENY OR CONDITION THE INTRODUCTION |
| | OF NEW SOURCES OF WASTEWATER TO THE WWF; OR |
| | (2) |
| | REQUIRE THE INDUSTRIAL USER TO DEMONSTRATE THAT |
| | IN-PLANT IMPROVEMENTS WILL MODIFY THE DISCHARGE TO SUCH |
| | A DEGREE AS TO BE ACCEPTABLE; AND/OR |
| | (3) |
| | REQUIRE PRETREATMENT OF THE INDUSTRIAL USER'S DISCHARGE |
| | TO ENSURE COMPLIANCE WITH THIS ARTICLE; AND/OR |
| | (4) |
| | REQUIRE PAYMENT OF AN INDUSTRIAL WASTE SURCHARGE TO |
| | COVER THE ADDED COST OF HANDLING AND TREATING EXCESS |
| | LOADS IMPOSED ON THE WWF BY SUCH DISCHARGE. SURCHARGE |
| | AMOUNTS SHALL BE ESTABLISHED BY A RESOLUTION OF THE |
| | CITY, TOGETHER WITH A SCHEDULE OF RATES AND FEES OF THE |
| | WWF. IMPOSITION OF INDUSTRIAL WASTE SURCHARGES FOR THE |
| | RECOVERY OF TREATMENT COSTS DOES NOT REPLACE OR |
| | SUPERSEDE THE REQUIREMENTS FOR PRETREATMENT FACILITIES, |
| | SHOULD THEY BE FOUND NECESSARY BY THE CITY. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |