| Date |
Text |
| 2022-04-27 17:33:11 | 1ST REVIEW FBC-2020 PLUMBING/ MED-GAS |
| | PERMIT- 22020213 |
| | 4/28/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | NFPA-99-2018 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. PLEASE REVIEW THE COMMENTS |
| | BELOW AND NOTE THAT INSTALLATION OF THE MED GAS SYSTEM |
| | MAY BE DONE UNDER A SEPARATE PERMIT. |
| | |
| | 1) SHEET P103: REFER TO SEC. 15.1.1- 15.1.4 NFPA 99 AND |
| | INDICATE ON THE PLAN THE CATEGORY OF THE MED GAS |
| | SYSTEM- CATEGORY 1, 2, 3 OR 4. FOR PURPOSE OF REVIEW IT |
| | IS ASSUMED THE SYSTEM IS CATEGORY 1. |
| | |
| | 2) P103 & P501: LABEL THE GAS CYLINDERS IN DETAIL |
| | 10/P501 AS EITHER O2 OR N2O. INDICATE THE CU. FT. |
| | CAPACITIES OF THE CYLINDERS AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS- SECS. 15.3.3.1.1 & 5.1.3.1.1 NFPA 99. |
| | THE CYLINDERS SHALL BE DESIGNED, FABRICATED, TESTED AND |
| | STAMPED IN ACCORDANCE WITH REGULATIONS OF DOT, |
| | TRANSPORT CANADA (TC) TRANSPORTATION OF DANGEROUS GOODS |
| | REGULATIONS, OR THE ASME BOILER AND PRESSURE VESSEL |
| | CODE. |
| | |
| | 3) P103 & P501: PROVIDE DOOR SIGNAGE DETAILS FOR THE |
| | GAS STORAGE CLOSET IN COMPLIANCE WITH SECS. 15.3.2.1 & |
| | 5.1.3.1.9 NFPA 99. |
| | |
| | 4) A101, P103, & P105: THE GAS ROOM MUST BE SEPARATED |
| | FROM OTHER AREAS OF THE BUILDING BY WALLS AND FLOORS |
| | HAVING BY A 1-HR. RATED FIRE RESISTANCE RATING WITH |
| | DOORS AND OTHER OPENING PROTECTIVES HAVE A 3/4 -HR. |
| | FIRE PROTECTION RATING- SECS.15.3.2.1 & 5.1.3.3.2 NFPA |
| | 99. SEE RELATED CODE SECTIONS-SEC. 415.10.2 FBC B, SEC. |
| | 9.3.6.6 NFPA 99, SEC. 6.4 NFPA, SEC. 502.9 FBC M. |
| | |
| | 5) P103 & P501: FOR CYLINDERS EQUIPPED WITH RELIEF |
| | VALVES PLEASE PROVIDE VALVE VENTING DETAILS- SECS. |
| | 15.3.2.1 & 5.1.3.5.6.1 NFPA 99. INCLUDE THE TYPES AND |
| | SIZES OF VENT PIPING, PIPING RUNS AND DISCHARGE |
| | LOCATIONS. |
| | |
| | 6) P103 & P501: CONTINUOUS MECHANICAL VENTILATION AT A |
| | RATE OF 1 CFM PER 5 CU. FT. OF FLUID SHALL BE PROVIDED, |
| | AND NOT LESS THAN 50 CFM OR MORE THAN 500 CFM- SECS. |
| | 15.3.2.1, 5.1.3.3.3.1, 19.3.6.5.3.1 & 9.3.6.5.3.2 NFPA |
| | 99. |
| | |
| | 7) P103 & P501: THE EXHAUST INLET SHALL FOR THE |
| | CYLINDER CLOSET SHALL BE UNOBSTRUCTED AND DRAW AIR |
| | WITHIN 1 FT. OF THE FLOOR ADJACENT TO THE CYLINDERS- |
| | SECS. 15.3.2.1, 5.1.3.3.3.1 & 9.3.6.5.3.3 NFPA 99. |
| | |
| | 8) P103 & P501: INDICATE HOW MAKEUP AIR FOR THE EXHAUST |
| | WILL BE PROVIDED- SECS. 15.3.2.1, 5.1.3.3.3.1 & |
| | 9.3.6.5.3.7 NFPA 99. |
| | |
| | 9) P103 & P501 DETAIL 10/P510: LABEL THE TYPES AND |
| | SIZES OF FLEXIBLE SUPPLY CONNECTORS FROM THE TANK TO |
| | THE MANIFOLD- SEC. 5.1.10.11.6.1 NFPA 99 B) SHOW |
| | SHUTOFF VALVE, RELIEF VALVE AND CHECK VALVE LOCATIONS- |
| | SEC. 5.1.4.1.1 NFPA 99. |
| | |
| | 10) P103 & P501: SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | FOR ALL EQUIPMENT AND PIPING IN THE GAS ROOM INCLUDING |
| | THE MANIFOLD, ALARM SYSTEM, PIPING, REGULATORS, VALVES, |
| | AND FLEX HOSES- SECS. 15.3.2.1.4, 15.3.2.1.6, 15.3.2.11 |
| | NFPA 99. SHOW THE LOCATIONS OF RELIEF VALVES AND |
| | PROVIDE RELIEF VALVE VENTING DETAILS INCLUDING TYPE OF |
| | VENT PIPING, VENT PIPING RUN AND DISCHARGE LOCATION- |
| | SEC. 15.3.2.11 NFPA 99. |
| | |
| | 11) P103 & P501: PROVIDE 02, N20 PIPING SPECIFICATIONS |
| | AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECS. |
| | 15.3.2.8, 5.1.10.1- 5.1.10.1.8 NFPA 99. A) INDICATE THE |
| | TYPE OF FITTINGS OR TECHNIQUES TO BE USED FOR PIPING |
| | TURNS, OFFSETS, AND OTHER CHANGES IN DIRECTION- SEC. |
| | 5.1.10.3.1 ITEMS 1-5 NFPA 99. B) PROVIDE PIPE SUPPORT |
| | AND HANGING DETAILS- SEC. 5.1.10.11.4 NFPA 99. C) |
| | PROVIDE PIPE LABELING DETAILS- SE. 5.1.11.1.1 NFPA 99. |
| | |
| | 12) P103: PROVIDE NOTES OR SYMBOLS TO SHOW THE |
| | LOCATIONS OF ALL SHUTOFF VALVES FOR THE GAS PIPING |
| | SYSTEMS- SECS. 5.1.4.1.1- 5.1.4.7 NFPA 99. A) PROVIDE |
| | VALVE LABELING DETAILS- SEC. 5.1.11.2.1. |
| | |
| | 13) P103: PROVIDE A GAS STATION INLET AND OUTLET |
| | DETAIL- SECS. 15.3.2.3 & 5.1.5 NFPA 99. A) PROVIDE |
| | STATION LABELING DETAILS- SEC. 5.1.11.3.1. |
| | |
| | 14) P103, P501, & P601: PROVIDE MANUFACTURER'S |
| | SPECIFICATIONS FOR ALL COMPONENTS OF THE WAGD SYSTEM- |
| | SECS. 15.3.2.1.7, 5.1.3.8- 5.1.3.8.3 NFPA 99. A) |
| | PROVIDE EXHAUST DETAILS- SEC. 5.1.3.7.7 NFPA 99. |
| | |
| | 15) P103, P501 & P601: SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE AIR COMPRESSOR AND VACUUM PUMP- |
| | SECS. 15.3.3.3.4.1 & 15.3.3.5.2.1 NFPA 99. |
| | |
| | 16) P103, P501, P601: PROVIDE COMPRESSED AIR AND VACUUM |
| | PIPING AND FITTING SPECIFICATIONS- SEC. 15.3.3.7.1- |
| | 15.3.3.7.3.4 NFPA 99. A) SHOW ALL SHUTOFF VALVE |
| | LOCATIONS FOR THE SYSTEMS. |
| | |
| | 17) P103, P501, P601: PROVIDE COMPRESSOR INTAKE AND |
| | VACUUM EXHAUST PIPING DIAGRAMS SHOWING THE TYPES AND |
| | SIZES OF PIPING, PIPING RUNS AND TERMINATION LOCATIONS |
| | WITH CLEARANCE DISTANCE MEASUREMENTS TO OTHER AIR |
| | INTAKES AND EXHAUST OUTLETS OR OPENINGS INTO THE |
| | BUILDING- SEC. 5.1.3.6.3.11 & 5.1.3.7.7.1 NFPA 99, SEC. |
| | 107.2.1 WPB. |
| | |
| | 18) P103: INDICATE HOW THE EQUIPMENT ROOM WILL BE |
| | VENTILATED- SEC. 15.3.3.2.3 NFPA 99. |
| | |
| | 19) P103: PLACE A NOTE ON THE PLAN TO INDICATE THE |
| | MED-GAS SYSTEM INSTALLED SHALL BE CERTIFIED IN |
| | ACCORDANCE WITH ASSE 6010- SEC. 5.1.10.11.10.2 NFPA 99. |
| | |
| | 20) PLEASE NOTE THE COPIED SECTIONS BELOW DERIVED FROM |
| | THE THE CITY OF WEST PALM BEACH CODE OF ORDINANCES |
| | PERTAINING TO DENTAL AND MEDICAL FACILITY WASTE |
| | DISPOSAL. NOTE IN PARTICULAR SEC.90-126(I1) CONCERNING |
| | THE VACUUM SYSTEM. |
| | |
| | SECS. 90-126 (H-M) |
| | ALL OWNERS AND OPERATORS OF DENTAL FACILITIES THAT |
| | REMOVE OR PLACE AMALGAM FILLINGS SHALL COMPLY WITH THE |
| | FOLLOWING REPORTING AND WASTE MANAGEMENT PRACTICES: |
| | (1) |
| | FOR EXISTING SOURCES, A ONE-TIME COMPLIANCE REPORT IS |
| | DUE NO LATER THAN 90 DAYS AFTER TRANSFER OF OWNERSHIP. |
| | (2) |
| | FOR NEW SOURCES, A ONE-TIME COMPLIANCE REPORT IS DUE |
| | WITHIN 90 DAYS OF THE START OF DISCHARGE TO THE SEWER |
| | COLLECTION SYSTEM. |
| | (3) |
| | NO PERSON SHALL RINSE CHAIRSIDE TRAPS, VACUUM SCREENS, |
| | OR AMALGAM SEPARATORS EQUIPMENT IN A SINK OR OTHER |
| | CONNECTION TO THE SANITARY SEWER. |
| | (4) |
| | OWNERS AND OPERATORS OF DENTAL FACILITIES SHALL ENSURE |
| | THAT ALL STAFF MEMBERS WHO HANDLE AMALGAM WASTE ARE |
| | TRAINED IN PROPER HANDLING, MANAGEMENT AND DISPOSAL OF |
| | MERCURY-CONTAINING MATERIAL AND FIXER-CONTAINING |
| | SOLUTIONS AND SHALL MAINTAIN TRAINING RECORDS THAT |
| | SHALL BE AVAILABLE FOR INSPECTION BY THE CITY |
| | INDUSTRIAL PRETREATMENT DIVISION DURING NORMAL BUSINESS |
| | HOURS. |
| | (5) |
| | AMALGAM WASTE SHALL BE STORED AND MANAGED IN ACCORDANCE |
| | WITH THE INSTRUCTIONS OF THE RECYCLER OR HAULER OF SUCH |
| | MATERIALS. |
| | (6) |
| | BLEACH AND OTHER CHLORINE-CONTAINING DISINFECTANTS |
| | SHALL NOT BE USED TO DISINFECT THE VACUUM LINE SYSTEM. |
| | (7) |
| | THE USE OF BULK MERCURY IS PROHIBITED. ONLY |
| | PRE-CAPSULATED DENTAL AMALGAM IS PERMITTED. |
| | (I) |
| | ALL OWNERS AND OPERATORS OF DENTAL VACUUM SUCTION |
| | SYSTEMS, EXCEPT AS SET FORTH IN SUBSECTIONS (J) AND (K) |
| | OF THIS SECTION, SHALL COMPLY WITH THE FOLLOWING: |
| | (1) |
| | AN ISO 11143 OR ANSI/ADA STANDARD NO. 108 CERTIFIED |
| | AMALGAM SEPARATOR OR EQUIVALENT DEVICE SHALL BE |
| | INSTALLED FOR EACH DENTAL VACUUM SUCTION SYSTEM. THE |
| | INSTALLED DEVICE MUST BE ISO 11143 OR ANSI/ADA STANDARD |
| | NO. 108 CERTIFIED AS CAPABLE OF REMOVING A MINIMUM OF |
| | 95 PERCENT OF AMALGAM. THE AMALGAM SEPARATOR SYSTEM |
| | SHALL BE CERTIFIED AT FLOW RATES COMPARABLE TO THE FLOW |
| | RATE OF THE ACTUAL VACUUM SUCTION SYSTEM OPERATION. |
| | NEITHER THE SEPARATOR DEVICE NOR THE RELATED PLUMBING |
| | SHALL INCLUDE AN AUTOMATIC FLOW BYPASS. FOR FACILITIES |
| | THAT REQUIRE AN AMALGAM SEPARATOR THAT EXCEEDS THE |
| | PRACTICAL CAPACITY OF ISO 11143 TEST METHODOLOGY, A |
| | NON-CERTIFIED SEPARATOR WILL BE ACCEPTED, PROVIDED THAT |
| | SMALLER UNITS FROM THE SAME MANUFACTURER AND OF THE |
| | SAME TECHNOLOGY ARE ISO-CERTIFIED. |
| | (2) |
| | PROOF OF CERTIFICATION AND INSTALLATION RECORDS SHALL |
| | BE SUBMITTED TO THE CITY INDUSTRIAL PRETREATMENT |
| | DIVISION WITHIN 30 DAYS OF INSTALLATION. |
| | (3) |
| | AMALGAM SEPARATORS SHALL BE MAINTAINED IN ACCORDANCE |
| | WITH MANUFACTURER RECOMMENDATIONS. INSTALLATION, |
| | CERTIFICATION, AND MAINTENANCE RECORDS SHALL BE |
| | AVAILABLE FOR IMMEDIATE INSPECTION UPON REQUEST |
| | THEREFOR BY THE CITY INDUSTRIAL PRETREATMENT DIVISION |
| | DESIGNEE DURING NORMAL BUSINESS HOURS. RECORDS SHALL BE |
| | MAINTAINED FOR A MINIMUM OF THREE YEARS. |
| | (J) |
| | FACILITIES WITH VACUUM SUCTION SYSTEMS THAT MEET ALL |
| | THE FOLLOWING CONDITIONS MAY APPLY TO THE CITY |
| | INDUSTRIAL PRETREATMENT DIVISION FOR AN EXEMPTION TO |
| | THE REQUIREMENTS OF SUBSECTION (I) OF THIS SECTION: |
| | (1) |
| | THE SYSTEM IS A DRY VACUUM PUMP SYSTEM WITH AN |
| | AIR-WATER SEPARATOR. |
| | (2) |
| | THE SEDIMENTATION TANK IS NON-BOTTOM DRAINING, WITH THE |
| | DRAIN ABOVE THE ANTICIPATED MAXIMUM LEVEL OF |
| | ACCUMULATED SLUDGE. |
| | (3) |
| | EVIDENCE OF REGULAR PUMP OUTS BY A LICENSED HAULER (A |
| | MINIMUM OF ONCE A YEAR, OR MORE OFTEN IF EITHER |
| | DIRECTED BY THE MANUFACTURER OR NECESSARY TO KEEP |
| | SOLIDS FROM EXITING THROUGH THE DRAIN) IS MAINTAINED |
| | AND OPEN TO INSPECTION BY CITY STAFF DURING NORMAL |
| | BUSINESS HOURS. |
| | (4) |
| | THE SYSTEM HAS NO DIRECT DISCHARGE PIPE TO THE SEWER ON |
| | THE BOTTOM OF THE SEDIMENTATION TANK. |
| | AN OWNER OR OPERATOR WHOSE FACILITY MEETS CONDITIONS |
| | (1) THROUGH (4) MAY APPLY FOR THIS EXEMPTION BY WRITTEN |
| | LETTER TO THE CITY INDUSTRIAL PRETREATMENT DIVISION. AN |
| | IPP DESIGNEE WILL REVIEW THE SYSTEM AND, IF THE |
| | EXEMPTION IS APPROVED, SHALL PROVIDE A WRITTEN LETTER |
| | OF EXEMPTION. |
| | AN EXEMPTION OBTAINED PURSUANT TO THIS SUBSECTION (J) |
| | SHALL EXPIRE UPON INSTALLATION OF A NEW VACUUM SYSTEM. |
| | UPON EXPIRATION OF THE EXEMPTION, THE FACILITY SHALL |
| | COMPLY WITH SUBSECTION (I) OF THIS SECTION BEFORE |
| | COMMENCING FURTHER OPERATION. |
| | (K) |
| | DENTAL DISCHARGERS THAT EXCLUSIVELY PRACTICE ONE OR |
| | MORE OF THE FOLLOWING SPECIALTIES ARE NOT SUBJECT TO |
| | THE REQUIREMENTS OF THIS SECTION: (1) ORTHODONTICS; (2) |
| | PERIODONTICS; (3) ORAL AND MAXILLOFACIAL SURGERY; (4) |
| | RADIOLOGY; (5) ORAL PATHOLOGY OR ORAL MEDICINE; (6) |
| | ENDODONTISTRY AND PROSTHODONTISTRY. |
| | (L) |
| | DENTAL PRACTICES THAT DO NOT PLACE DENTAL AMALGAM, AND |
| | DO NOT REMOVE AMALGAM EXCEPT IN LIMITED EMERGENCY OR |
| | UNPLANNED, UNANTICIPATED CIRCUMSTANCES, ARE EXEMPT FROM |
| | THE REQUIREMENTS OF THIS PART, PROVIDED THE DENTAL |
| | PRACTICE: |
| | (1) |
| | SUBMITS THE FOLLOWING STATEMENT TO THE CITY INDUSTRIAL |
| | PRETREATMENT DIVISION, SIGNED BY A RESPONSIBLE |
| | CORPORATE OFFICER, GENERAL PARTNER, PROPRIETOR, OR A |
| | DULY AUTHORIZED REPRESENTATIVE BY THE APPLICABLE |
| | COMPLIANCE DEADLINE IDENTIFIED IN SECTION 90-126(H)(1) |
| | AND 90-126(H)(2): |
| | "THIS FACILITY IS A DENTAL DISCHARGER SUBJECT TO THIS |
| | RULE AND DOES NOT PLACE OR REMOVE DENTAL AMALGAM EXCEPT |
| | IN LIMITED EMERGENCY OR UNPLANNED, UNANTICIPATED |
| | CIRCUMSTANCES. I AM A RESPONSIBLE CORPORATE OFFICER, A |
| | GENERAL PARTNER OR PROPRIETOR (IF THE FACILITY IS A |
| | PARTNERSHIP OR SOLE PROPRIETORSHIP), OR A DULY |
| | AUTHORIZED REPRESENTATIVE IN ACCORDANCE WITH THE |
| | REQUIREMENTS OF 403.12(L) OF THE ABOVE NAMED DENTAL |
| | FACILITY, AND CERTIFY UNDER PENALTY OF LAW THAT THIS |
| | DOCUMENT AND ALL ATTACHMENTS WERE PREPARED UNDER MY |
| | DIRECTION OR SUPERVISION IN ACCORDANCE WITH A SYSTEM |
| | DESIGNED TO ASSURE THAT QUALIFIED PERSONNEL PROPERLY |
| | GATHER AND EVALUATE THE INFORMATION SUBMITTED. BASED ON |
| | MY INQUIRY OF THE PERSON OR PERSONS WHO MANAGE THE |
| | SYSTEM, OR THOSE PERSONS DIRECTLY RESPONSIBLE FOR |
| | GATHERING THE INFORMATION, THE INFORMATION SUBMITTED |
| | IS, TO THE BEST OF MY KNOWLEDGE AND BELIEF, TRUE, |
| | ACCURATE, AND COMPLETE. I AM AWARE THAT THERE ARE |
| | SIGNIFICANT PENALTIES FOR SUBMITTING FALSE INFORMATION, |
| | INCLUDING THE POSSIBILITY OF FINE AND IMPRISONMENT FOR |
| | KNOWING VIOLATIONS." |
| | (2) |
| | REMOVES DENTAL AMALGAM FOR LIMITED EMERGENCY OR |
| | UNPLANNED, UNANTICIPATED CIRCUMSTANCES, LESS THAN TEN |
| | TIMES PER YEAR OR NO MORE THAN TEN PERCENT OF DENTAL |
| | PROCEDURES; AND |
| | (3) |
| | THE DENTAL PRACTICE NOTIFIES THE CITY OF ANY CHANGES |
| | AFFECTING THE APPLICABILITY OF THIS CERTIFICATION. |
| | (4) |
| | DISPOSAL OF HAULED WASTE FROM DENTAL FACILITIES TO THE |
| | SANITARY SEWER IS PROHIBITED IN ACCORDANCE WITH SECTION |
| | 90-126(B)(8). |
| | (M) |
| | CONTROL OF DISCHARGE. IF ANY WASTES OR WASTEWATERS ARE |
| | DISCHARGED, OR ARE PROPOSED TO BE DISCHARGED, TO THE |
| | WWF WHICH CONTAIN THE SUBSTANCES OR POSSESS THE |
| | CHARACTERISTICS ENUMERATED IN THIS SECTION AS |
| | PROHIBITED BY THIS ARTICLE, DO NOT MEET APPLICABLE |
| | PRETREATMENT STANDARDS AND REQUIREMENTS, AND/OR WHICH |
| | MAY HAVE A DELETERIOUS EFFECT UPON THE WWF, ITS |
| | PROCESSES, EQUIPMENT, OR RECEIVING WATERS, OR WHICH |
| | OTHERWISE CREATE A HAZARD TO LIFE OR CONSTITUTE A |
| | PUBLIC NUISANCE, THE CITY MAY: |
| | (1) |
| | REJECT THE WASTES OR DENY OR CONDITION THE INTRODUCTION |
| | OF NEW SOURCES OF WASTEWATER TO THE WWF; OR |
| | (2) |
| | REQUIRE THE INDUSTRIAL USER TO DEMONSTRATE THAT |
| | IN-PLANT IMPROVEMENTS WILL MODIFY THE DISCHARGE TO SUCH |
| | A DEGREE AS TO BE ACCEPTABLE; AND/OR |
| | (3) |
| | REQUIRE PRETREATMENT OF THE INDUSTRIAL USER'S DISCHARGE |
| | TO ENSURE COMPLIANCE WITH THIS ARTICLE; AND/OR |
| | (4) |
| | REQUIRE PAYMENT OF AN INDUSTRIAL WASTE SURCHARGE TO |
| | COVER THE ADDED COST OF HANDLING AND TREATING EXCESS |
| | LOADS IMPOSED ON THE WWF BY SUCH DISCHARGE. SURCHARGE |
| | AMOUNTS SHALL BE ESTABLISHED BY A RESOLUTION OF THE |
| | CITY, TOGETHER WITH A SCHEDULE OF RATES AND FEES OF THE |
| | WWF. IMPOSITION OF INDUSTRIAL WASTE SURCHARGES FOR THE |
| | RECOVERY OF TREATMENT COSTS DOES NOT REPLACE OR |
| | SUPERSEDE THE REQUIREMENTS FOR PRETREATMENT FACILITIES, |
| | SHOULD THEY BE FOUND NECESSARY BY THE CITY. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |