2022-04-26 14:21:301ST REVIEW FMC
 PERMIT: 22020213
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THE NEW SYSTEMS. FMC 312.1
  
 2) PLEASE ADD THE DUCT SIZES TO ALL DUCTS LEADING TO
 THE SUPPLY AND RETURN GRILLES. FBC 107.2.1
  
 3) SHEET M101 FOOT NOTE 6 CALLS FOR A 1 HOUR FIRE DUCT
 WRAP. PLEASE PROVIDE A DETAIL OF THIS FIRE RATED DUCT
 WRAP WITH THIS DESIGN. DOES THE WRAP INCLUDE THE EF-4
 EXHAUST FAN? DOES THE 1 HOUR DUCT FIRE WRAP CONTINUE TO
 THE EXHAUST DUCT TERMINATION LOCATION? FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  