Plan Review Notes
Plan Review Notes For Permit 22020199
Permit Number 22020199
Review Stop M
Sequence Number 3
Notes
Date Text
2022-02-22 09:44:012ND REVIEW FBC-2020 MECHANICAL
 PERMIT-22020199
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE UPDATE THE PERMIT APPLICATION TO SHOW THIS IS
 VERTICAL GREASE DUCT FOR FUTURE TENANT.
  
 2) PLEASE PROVIDE A DRAWING SHOWING THE LOCATION OF
 THIS VERTICAL GREASE DUCT IN THIS EXISTING BUILDING ON
 EACH FLOOR. THIS SHOULD SHOW EACH FLOOR AND HOW THE
 GREASE DUCT WILL BE ACCESSED AT EACH FLOOR. FBC M
 506.3.8
  
 4) PLEASE SHOW ALL CHANGES OF DIRECTION FOR THIS
 VERTICAL GREASE DUCT AND THE CLEANOUTS REQUIRED FOR THE
 CHANGES IN DIRECTION. FBC M 506.3.8
  
 5) PLEASE SHOW THE UL LISTING FOR THE FIRE SEPARATION
 FOR THE TENANT SPACE SEPARATION AT THE FLOOR CUT OUT
 FOR THE DUCT. FBC 107.2.1
  
 6) THERE IS A NOTE ON THE DRAWING SUBMITTED CALLING FOR
 A DEDICATED SHAFT, PLEASE PROVIDE THE ARCHITECTURAL
 DRAWINGS OF THIS SHAFT AND THE UL LISTING FOR THE FIRE
 RATING. FBC 107.2.1
  
  
 7) HOOD PLAN SHEET:2 MENTIONS NOTES BUT THERE ARE NO
 NOTES ON THIS DRAWING. PLEASE SHOW THESE NOTES. FBC
 107.2.1
  
  
  
 9) SHEET M-03 ROOF PLAN: UNDER DISCHARGE NOTES THE 2ND
 NOTE INDICATES A MINIMUM OF 40 INCHES ABOVE THE ROOF
 STRUCTURE. AS THIS AREA OF THE BUILDING WILL HAVE
 PEDESTRIANS THE HOOD EXHAUST WILL NEED TO MEET FBC M
 SECTION 506.3.13.3 EXHAUST OUTLETS SHALL BE LOCATED NOT
 LESS THAN 10 FEET (3048 MM) HORIZONTALLY FROM PARTS OF
 THE SAME OR CONTIGUOUS BUILDINGS, ADJACENT BUILDINGS
 AND ADJACENT PROPERTY LINES AND SHALL BE LOCATED NOT
 LESS THAN 10 FEET (3048 MM) ABOVE THE ADJOINING GRADE
 LEVEL.
  
 10) SHEET M-03: PLEASE SHOW THE DIRECTION OF THE
 EXHAUST FLOW AT THE TERMINATION LOCATION. FBC M
 506.3.13.3 EXCEPTION: EXHAUST OUTLETS SHALL TERMINATE
 NOT LESS THAN 5 FEET (1524 MM) HORIZONTALLY FROM PARTS
 OF THE SAME OR CONTIGUOUS BUILDING, AN ADJACENT
 BUILDING, ADJACENT PROPERTY LINE AND AIR INTAKE
 OPENINGS INTO A BUILDING WHERE AIR FROM THE EXHAUST
 OUTLET DISCHARGES AWAY FROM SUCH LOCATIONS.
  
 11) THIS PROJECT WAS STARTED WITHOUT PERMITS AND THE
 FIELD APPLIED GREASE DUCT ENCLOSURE HAS ALREADY BEEN
 INSTALLED. THERE HAVE BEEN NO GREASE DUCT TEST. THE
 FIELD APPLIED GREASE DUCT ENCLOSURE SHALL BE REMOVED
 AND THE GREASE DUCT TEST SHALL BE PERFORMED AND PASSED
 BEFORE THE FIELD APPLIED GREASE DUCT ENCLOSURE CAN BE
 REINSTALLED. FBC M 506.3.2.5
  
  
 13) SHEET M-03: PLEASE SHOW THE FIELD APPLIED GREASE
 DUCT ENCLOSURE ON THE ROOF GREASE DUCT AND HOW THIS
 WILL BE PROTECTED FROM THE WEATHER. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  