| Plan Review Notes For Permit 22020199 |
| Permit Number |
22020199 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-02-22 10:45:30 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) RESOLVED. PER THE RESPONSE LETTER, NO FIRE-RESISTIVE | | | SHAFTS WILL BE CONSTRUCTED. | | | | | | 2) RESOLVED. THE GREASE DUCT WILL BE WRAPPED IN FIRE | | | WRAP AND WILL TERMINATE AT THE KITCHEN EXHAUST HOOD. | | | THERE WILL NOT BE ANY FIRE-RESISTIVE SHAFTS | | | CONSTRUCTED. | | | | | | 3) NOT RESOLVED. [ SPECIFY THE LISTED ASSEMBLY AND THE | | | SPECIFIC MATERIALS AND SPECIFICATIONS FOR IT'S | | | INSTALLATION.] THAT WILL BE USEDPROVIDE A DETAIL | | | SHOWING HOW THE DRAFTSTOPPING MATERIAL AROUND THE | | | GREASE DUCT PENETRATION WILL BE SUPPORTED. SHOW AN | | | APPROVED LISTED ASSEMBLY FOR A TWO HOUR FIRE-RESISTIVE | | | RATING. FBC 718.3.1 | | | | | | 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | | | 5) NEW COMMENT. NOTE: IF A FIRE-RESISTIVE RATED SHAFT | | | WILL BE CONSTRUCTED SUBMIT THE DETAILS FOR THE LISTED | | | SHAFT ASSEMBLY THAT WILL BE USED. FBC 713.1 |
|