2022-02-22 10:45:30PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) RESOLVED. PER THE RESPONSE LETTER, NO FIRE-RESISTIVE
 SHAFTS WILL BE CONSTRUCTED.
  
 2) RESOLVED. THE GREASE DUCT WILL BE WRAPPED IN FIRE
 WRAP AND WILL TERMINATE AT THE KITCHEN EXHAUST HOOD.
 THERE WILL NOT BE ANY FIRE-RESISTIVE SHAFTS
 CONSTRUCTED.
  
 3) NOT RESOLVED. [ SPECIFY THE LISTED ASSEMBLY AND THE
 SPECIFIC MATERIALS AND SPECIFICATIONS FOR IT'S
 INSTALLATION.] THAT WILL BE USEDPROVIDE A DETAIL
 SHOWING HOW THE DRAFTSTOPPING MATERIAL AROUND THE
 GREASE DUCT PENETRATION WILL BE SUPPORTED. SHOW AN
 APPROVED LISTED ASSEMBLY FOR A TWO HOUR FIRE-RESISTIVE
 RATING. FBC 718.3.1
  
 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
 5) NEW COMMENT. NOTE: IF A FIRE-RESISTIVE RATED SHAFT
 WILL BE CONSTRUCTED SUBMIT THE DETAILS FOR THE LISTED
 SHAFT ASSEMBLY THAT WILL BE USED. FBC 713.1