2022-02-14 10:26:471ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22020199
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE UPDATE THE PERMIT APPLICATION TO SHOW THIS IS
 VERTICAL GREASE DUCT FOR FUTURE TENANT.
  
 2) PLEASE PROVIDE A DRAWING SHOWING THE LOCATION OF
 THIS VERTICAL GREASE DUCT IN THIS EXISTING BUILDING.
 THIS SHOULD SHOW EACH FLOOR AND THE EXHAUST TERMINATION
 ON THE ROOF. THERE IS GREEN SPACE ON THIS ROOF, PLEASE
 SHOW WHERE THE TERMINATION LOCATION WILL BE LOCATED IN
 THIS GREEN SPACE AREA. FBC 107.2.1
  
 3) THE FIELD WRAPPED GREASE DUCT SHALL BE CONTINUOUSLY
 WRAPPED FROM THE ORIGINATION OF THE DUCT TO THE OUTLET
 TERMINAL. FBC M 506.3.11.2
  
 4) PLEASE SHOW ALL CHANGES OF DIRECTION FOR THIS
 VERTICAL GREASE DUCT AND THE CLEANOUTS REQUIRED FOR THE
 CHANGES IN DIRECTION. FBC M 506.3.8
  
 5) PLEASE SHOW THE UL LISTING FOR THE FIRE SEPARATION
 FOR THE TENANT SPACE SEPARATION, FLOOR, FBC 107.2.1
  
 6) THERE IS A NOTE ON THE DRAWING SUBMITTED CALLING FOR
 A DEDICATED SHAFT, PLEASE PROVIDE THE ARCHITECTURAL
 DRAWINGS OF THIS SHAFT AND THE UL LISTING FOR THE FIRE
 RATING. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  