| 2022-02-14 10:26:47 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-22020199 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE UPDATE THE PERMIT APPLICATION TO SHOW THIS IS |
| | VERTICAL GREASE DUCT FOR FUTURE TENANT. |
| | |
| | 2) PLEASE PROVIDE A DRAWING SHOWING THE LOCATION OF |
| | THIS VERTICAL GREASE DUCT IN THIS EXISTING BUILDING. |
| | THIS SHOULD SHOW EACH FLOOR AND THE EXHAUST TERMINATION |
| | ON THE ROOF. THERE IS GREEN SPACE ON THIS ROOF, PLEASE |
| | SHOW WHERE THE TERMINATION LOCATION WILL BE LOCATED IN |
| | THIS GREEN SPACE AREA. FBC 107.2.1 |
| | |
| | 3) THE FIELD WRAPPED GREASE DUCT SHALL BE CONTINUOUSLY |
| | WRAPPED FROM THE ORIGINATION OF THE DUCT TO THE OUTLET |
| | TERMINAL. FBC M 506.3.11.2 |
| | |
| | 4) PLEASE SHOW ALL CHANGES OF DIRECTION FOR THIS |
| | VERTICAL GREASE DUCT AND THE CLEANOUTS REQUIRED FOR THE |
| | CHANGES IN DIRECTION. FBC M 506.3.8 |
| | |
| | 5) PLEASE SHOW THE UL LISTING FOR THE FIRE SEPARATION |
| | FOR THE TENANT SPACE SEPARATION, FLOOR, FBC 107.2.1 |
| | |
| | 6) THERE IS A NOTE ON THE DRAWING SUBMITTED CALLING FOR |
| | A DEDICATED SHAFT, PLEASE PROVIDE THE ARCHITECTURAL |
| | DRAWINGS OF THIS SHAFT AND THE UL LISTING FOR THE FIRE |
| | RATING. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |