| Plan Review Notes For Permit 22020199 |
| Permit Number |
22020199 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-16 17:13:40 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT DRAWINGS THAT SHOW THE LISTED ASSEMBLY THAT | | | WILL BE USED TO CONSTRUCT THE PROPOSED 2 HOUR | | | FIRE-RESISTANCE RATED GREASE DUCT SHAFT. FBC 713.4 | | | | | | 2) SHOW COMPLIANCE WITH FBC 713.11 FOR HOW THE BOTTOM | | | OF THE SHAFT WILL BE ENCLOSED AT THE BOTTOM. | | | | | | 3) PROVIDE A DETAIL SHOWING HOW THE DRAFTSTOPPING | | | MATERIAL AROUND THE GREASE DUCT PENETRATION WILL BE | | | SUPPORTED. SHOW AN APPROVED LISTED ASSEMBLY FOR A TWO | | | HOUR FIRE-RESISTIVE RATING. FBC 718.3.1 | | | | | | 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
|