2022-08-04 15:02:412ND REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 22020197
 8/4/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS BELOW ARE BASED
 ON RESUBMITTED GAS PLANS
  
 1) GAS RISER: BASED ON TABLE 402.4(5) FBC FG FOR A
 2-PSI SYSTEM WITH 103 FT. TDL, A MINIMUM 1-1/4-INCH
 DIAMETER STEEL PIPE IS REQUIRED FROM THE METER TO THE
 TEE FOR THE TOTAL 2,022,000 BTU GAS LOAD. PLEASE SHOW
 THE PIPE DIAMETER ON THE DRAWING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  