| Plan Review Notes For Permit 22020197 |
| Permit Number |
22020197 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-08-04 15:02:41 | 2ND REVIEW FBC-2020 RES. FUEL GAS | | | PERMIT- 22020197 | | | 8/4/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. COMMENTS BELOW ARE BASED | | | ON RESUBMITTED GAS PLANS | | | | | | 1) GAS RISER: BASED ON TABLE 402.4(5) FBC FG FOR A | | | 2-PSI SYSTEM WITH 103 FT. TDL, A MINIMUM 1-1/4-INCH | | | DIAMETER STEEL PIPE IS REQUIRED FROM THE METER TO THE | | | TEE FOR THE TOTAL 2,022,000 BTU GAS LOAD. PLEASE SHOW | | | THE PIPE DIAMETER ON THE DRAWING. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|