| 2022-05-12 11:31:10 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) NOT RESOLVED. [ THE ENGINEERING THAT WAS SUBMITTED |
| | FOR THE PREFABRICATED GENERATOR PAD AND THE STAND ARE |
| | NOT ACCEPTABLE. THE PROJECT IS LOCATED IN EXPOSURE |
| | CATEGORY D AND A 170 MPH VULT WIND SPEED. THE DRAWING |
| | NEEDS TO SPECIFY THE MAXIMUM DIMENSIONS AND THE MINIMUM |
| | WEIGHT REQUIREMENTS FOR THE GENERATOR. |
| | |
| | 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 |
| | FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE |
| | OPENINGS. |
| | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS |
| | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM |
| | ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, |
| | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS |
| | AND LOADING DOCKS. |
| | |
| | 3) FBC AMENDMENTS 107.2.1 ELECTRONICALLY SUBMITTED |
| | DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT OR |
| | ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE |
| | OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF |
| | DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN |
| | APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER |
| | DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE |
| | ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE |
| | AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO |
| | PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE |
| | ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & FAC 61G15 |
| | |
| | 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |