2022-03-23 15:09:13PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT SIGNED AND SEALED SITE SPECIFIC ENGINEERING
 FOR THE PREFABRICATED GENERATOR PAD. FBC AMENDMENTS
 107.2.1 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED
 TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE
 ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED
 AND SEALED PAPER VERSION OF DRAWINGS. AFTER THE
 ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 &
 FAC 61G15
  
 2) THE GENERATOR PLATFORM DRAWING SPECIFIES A 144 MPH
 WIND SPEED. THIS PROJECT IS LOCATED IN A 150 MPH WIND
 SPEED AND EXPOSURE D. FBC-R 301.2.1
  
 3) SUBMIT A SIGNED AND SEALED ENGINEER'S EVALUATION
 WITH CALCULATIONS FOR THE GENERATOR STAND AND SLAB
 ASSEMBLY TO SHOW THAT IT WILL MEET THE WINDLOADS. FBC
 AMENDMENTS 107.2.1.2
  
 4) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
  
 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  