| 2022-03-23 15:09:13 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT SIGNED AND SEALED SITE SPECIFIC ENGINEERING |
| | FOR THE PREFABRICATED GENERATOR PAD. FBC AMENDMENTS |
| | 107.2.1 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED |
| | TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE |
| | ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED |
| | AND SEALED PAPER VERSION OF DRAWINGS. AFTER THE |
| | ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE |
| | CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT |
| | TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL |
| | HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE |
| | DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE |
| | SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & |
| | FAC 61G15 |
| | |
| | 2) THE GENERATOR PLATFORM DRAWING SPECIFIES A 144 MPH |
| | WIND SPEED. THIS PROJECT IS LOCATED IN A 150 MPH WIND |
| | SPEED AND EXPOSURE D. FBC-R 301.2.1 |
| | |
| | 3) SUBMIT A SIGNED AND SEALED ENGINEER'S EVALUATION |
| | WITH CALCULATIONS FOR THE GENERATOR STAND AND SLAB |
| | ASSEMBLY TO SHOW THAT IT WILL MEET THE WINDLOADS. FBC |
| | AMENDMENTS 107.2.1.2 |
| | |
| | 4) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 |
| | FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE |
| | OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE |
| | OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 |
| | MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS |
| | VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, |
| | PARKING LOTS AND LOADING DOCKS. |
| | |
| | 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |