| Notes |
| Date |
Text |
| 2022-02-11 15:30:06 | 1ST PLUMBING REVIEW | | | | | | V7 FPC ? 2020 FLORIDA PLUMBING CODE | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. V7 FPC 607.1.1 -- TEMPERATURE LIMITING MEANS --- THE | | | THERMOSTAT FOR THE WATER CANNOT BE THE LIMIT FOR "HOT | | | WATER" DELIVERY. PLEASE PROVIDE PROTECTION FOR EACH | | | "HOT WATER" OUTLET EITHER INDIVIDUALLY OR AT THE | | | SOURCE. THIS IS IN ADDITION TO THE LIMIT FOR "TEMPERED | | | WATER" FOR THE PUBLIC HANDWASHING SINK. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|