2022-02-11 13:43:421ST PLUMBING REVIEW
  
 V7 FBC-RES ? 2020 FLORIDA RESIDENTIAL BUILDING CODE
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. V7 FBC-RES P3108.2.1 HORIZONTAL WET VENT -- YOUR
 RISER DIAGRAM SHOWS THE VENTED FIXTURE CONNECTION
 DOWNSTREAM OF TWO FIXTURES/TRAPS. ONLY ONE FIXTURE IS
 ALLOWED UPSTREAM OF THE VENTED FIXTURE CONNECTION.
 PLEASE RECONFIGURE AND RESUBMIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  