| Plan Review Notes For Permit 22020140 |
| Permit Number |
22020140 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-17 10:52:55 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-22020140 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FOR THIS PROJECT. FBC RES M403.7.1 | | | | | | 2) PLEASE SUBMIT A CODE COMPLIANT DRAWING THAT SHOWS | | | THE LOCATION OF THE NEW MECHANICAL SYSTEM AND HOW IT | | | WILL BE ACCESSED. IF THE NEW AHU IS IN A CLOSET PLEASE | | | SHOW THE RETURN AIR PATH BACK TO THE UNIT, LOUVERED | | | DOOR? FBC RES M1602.3 | | | | | | 3) PLEASE SHOW THE DRYER EXHAUST DUCT MATERIAL AND | | | TERMINATION LOCATION. FBC RES M1502 | | | | | | 4) PLEASE SHOW THE ANCHORING DETAILS FOR THE CONDENSING | | | UNIT. FBC RES M1307.2 | | | | | | 5) THE DESIGNER OF THE DRAWING MUST PRINT THEN SIGN | | | THEIR NAME ON THE DRAWING. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|