Plan Review Notes
Plan Review Notes For Permit 22020140
Permit Number 22020140
Review Stop E
Sequence Number 1
Notes
Date Text
2022-02-23 22:55:11ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN PROVIDED DOES NOT CLEARLY ANNOTATE WHAT WORK IS
 NEW AND WHERE ADDITION IS. APPLICATION SAYS "ADDITION
 AND REDO BATHROOMS" BUT PLAN SHOWN APPEARS TO BE FOR A
 FULL GUT REMODEL. PLEASE PROVIDE PLAN THAT CLEARLY
 SHOWS WHAT IS NEW AND EXISTING. FBC 107.2.1
  
 2. SEVERAL WALL SPACING RECEPTACLE VIOLATIONS
 THROUGHOUT HOUSE PER NEC 210.52. PROVIDE CORRECTIONS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  