2022-03-31 14:31:27RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22020140
  
 NOTE:
 ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1-LOT DRAINAGE
 PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE
 DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT
 WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES.
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. SEC.
 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 2- ENGINEER OF RECORD TO SPECIFY ALL ROOF LIVE AND DEAD
 LOADS. CLEARLY SPECIFY TRUSS TOP AND BOTTOM CHORDS LIVE
 AND DEAD LOADS INCLUDING THE ATTIC LIVE LOAD AS
 REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL.
 SEE FOOTNOTES "B" AND "G".
  
 3- MASTER BEDROOM EGRESS WINDOW. CLEARLY SPECIFY CLEAR
 OPENINGS OF HORIZONTAL ROLLING WINDOW TO VERIFY
 COMPLIANCE WITH THE MINIMUM CLEAR OPENING REQUIREMENTS
 OF SEC. R310.2.1 FBC-RESIDENTIAL.
  
 4- NEW OFFICE SPACE DOESN'T COMPLY WITH THE MINIMUM
 ROOM DIMENSIONS AND MINIMUM ROOM SQUARE FOOTAGE AS
 REQUIRED BY SEC. R304 FBC-RESIDENTIAL. REVISE AS
 REQUIRED TO COMPLY.
  
 5- REVISE ROOF SHEATHING NAILING SPACING. ROOF
 SHEATHING NEEDS TO BE NAILED WITH AT 4 INCHES O.C. IN
 THE FIELD AND EDGES AS REQUIRED BY SEC. R803.2.3.1 AND
 TABLE R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS
 SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR
 EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM
 REQUIREMENTS.
  
 NOTE: REVISE SPECIFICATIONS ON ALL PLANS AND WALL
 SECTIONS TO AVOID CONFLICTS/DELAYS.
  
 6- PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH
 THE NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT.
 SEC. R905.1.1.1 FBC-RESIDENTIAL.
 NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1
 FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE
 PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001.
 NOTE: PLANS SUBMITTED SPECIFY 3:12 ROOF PITCH.
 COORDINATE WITH SEC. R905.2.2 FBC-RESIDENTIAL.
  
 7- SPECIFY ATTIC ACCESS SIZE FOR THE NEW ADDITION. SEC.
 1101.1 FBC-EXISTING BUILDING. SEC. R807.1
 FBC-RESIDENTIAL.
  
 8- PROVIDE FIRE RATING SPECIFICATIONS FOR GARAGE DOOR
 LEADING TO THE INTERIOR OF THE HOUSE SHOWING COMPLIANCE
 WITH SEC. R302.5.1 FBC-RESIDENTIAL.
  
 9- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF SHINGLES. PRODUCT APPROVAL SUBMITTED IS
 INCOMPLETE. NEED TO PROVIDE COMPLETE FLORIDA PRODUCT
 APPROVAL INCLUDING THE FLORIDA PRODUCT APPROVAL COVER
 PAGE THAT CORRESPONDS TO THE DRAWINGS SUBMITTED. THE
 FLORIDA PRODUCT APPROVAL IS REQUIRED BECAUSE IT SHOWS
 IF PRODUCT IS APPROVED AND CURRENT CODE IN EFFECT.
 CHAPTER 553 F.S.
  
 B)ROOFING UNDERLAYMENT. PRODUCT APPROVAL SUBMITTED IS
 INCOMPLETE. ONLY THE FLORIDA PRODUCT APPROVAL COVER
 PAGE WAS UPLOADED. NEED TO UPLOAD THE INSTALLATION
 INSTRUCTIONS ALSO.
  
 C)WINDOWS TYPES SPECIFIED ON PLANS.
  
 D)INSWING AND OUTSWING EXTERIOR SWING DOORS SHOWN ON
 PLANS.
  
 10- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 11- ENERGY CALCULATIONS SUBMITTED:
 A)ENERGY CALCULATIONS FORM R405-2020 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER NAME, PERMIT OFFICE AND JURISDICTION
 NUMBER (THIS JURISDICTION IS 604700) . SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)CONDITIONED FLOOR AREA IS INCORRECT. ENTIRE REAR AREA
 OF THE HOUSE IS NEW. SEE PLANS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: TAKE THIS INTO CONSIDERATION WHEN DOING THE
 HEATING AND COOLING EQUIPMENT SIZING CALCULATIONS TO
 AVOID CONFLICTS/DELAYS.
  
 D) PROVIDE THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY
 CONSERVATION.
  
 E)ROOF TYPE SPECIFIED ON PAGE 2 IS INCORRECT. SEE PLANS
 AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 F)ATTIC VENT RATIO ON PAGE 2 IS INCORRECT. TYPICALLY,
 THE RATIO IS 1/150 NOT 1/300. SEC. R806.2
 FBC-RESIDENTIAL. SEE PLANS AND REVISE AS REQUIRED OR
 PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE
 COMPLETE DETAILS/SPECIFICATIONS SHOWING COMPLIANCE WITH
 THE 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC.
 R806.2 FBC-RESIDENTIAL. NOTE: ENGINEER OF RECORD NEEDS
 TO REVISE PLANS PRIOR TO SUBMITTAL.
  
 G)WINDOWS INFORMATION ON PAGE 3 IS INCORRECT. SEE
 PLANS/ELEVATIONS AND REVISE AS REQUIRED. NEED TO
 SPECIFY ALL WINDOWS SHOWN ON THE ADDITION (NOTE:
 COORDINATE WITH ITEM #11(C) ABOVE). PROVIDE CORRECT
 WINDOW ORIENTATION, AREA AND OVERHANG DEPTH AND
 SEPARATION. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H)GARAGE INFORMATION IS INCORRECT. GARAGE IS NOT PART
 OF THE ADDITION.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 12- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS.
 VALUATION WAS UPDATED TO $170, 000 +/-. THE PERMIT FEE
 BALANCE IS $929.88.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]