| 2022-04-14 13:52:08 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22020132 |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| | ISSUANCE. |
| | |
| | ***IMPORTANT*** |
| | ENERGY CALCULATIONS NEED TO BE SUBMITTED AND CERTIFIED |
| | BY THE OWNER OR AUTHORIZED AGENT BEFORE ISSUING THE |
| | PERMIT. |
| | |
| | 1- ROOF SHEATHING NAILING SPACING SPECIFIED ON SHEET |
| | S-2 DOESN'T COMPLY WITH TABLE R803.2.3.1 |
| | FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| | |
| | 2- GABLE END UPLIFT DIAGRAM SHOWN ON SHEET S-2 DOESN'T |
| | MATCH ROOF ZONES ZONES SPECIFIED ON FIGURE R301.2(7) |
| | FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| | |
| | 3- PLANS DON'T PROVIDE SPECIFICATIONS SHOWING HOW |
| | COMPLYING WITH THE NEW 2020 CODE REQUIREMENT FOR |
| | ROOFING UNDERLAYMENT SEC. R905.1.1.1 FBC-RESIDENTIAL. |
| | NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1 |
| | FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE |
| | PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001 |
| | |
| | 4-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | R101.5 FBC-ENERGY CONSERVATION. |
| | NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL |
| | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | 5- PRODUCT APPROVALS |
| | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| | FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| | |
| | A)SINGLE HUNG WINDOWS. |
| | B)ENTRY DOOR. |
| | C)GREAT ROOM SWING DOOR. |
| | D)ROOF SHINGLES. |
| | |
| | 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS |
| | NOTE: COORDINATE PRODUCT APPROVAL SUBMITTAL AFFIDAVIT |
| | ON SHEET A-1 WITH PRODUCT APPROVALS SUBMITTED TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | 7- DRAINAGE PLAN DRAWING C-1: REVISE PROPOSED DRAINAGE |
| | AT THE REAR AND RIGHT HAND SIDE OF THE PROPERTY. |
| | SURFACE DRAINAGE CAN NOT BE DIVERTED TO ADJACENT |
| | PROPERTIES. DRAINAGE WATER TO BE KEPT WITHIN THE LOT OR |
| | DIVERTED TOWARDS THE STREET. R401.3 FBC-RESIDENTIAL. |
| | SEC. 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY |
| | AMENDMENTS. |
| | |
| | 8- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW. |
| | VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S |
| | OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS |
| | REQUIRED BY SEC. 109.3 CITY AMENDMENTS. VALUATION WAS |
| | UPDATED TO $154,371.00. THE PERMIT FEE BALANCE IS |
| | $2884.68. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| | REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |