| | BUILDING REVIEW DENIED: |
| | |
| | 2B.) THE ROOF SHEATHING NAILING SPACING SPECIFICATIONS |
| | ON SHEET S-2 AT THE SIDE OF ROOF DIAGRAMS IS MISSING |
| | ZONE 2N. |
| | 6.) THE WIND DESIGN INFORMATION (ULTIMATE WIND SPEED & |
| | NOMINAL WIND SPEED) ON PLAN SHEET A-1 AT WALL PRESSURES |
| | NEEDS TO BE CHANGED TO MATCH THE ULTIMATE & NOMINAL |
| | WIND SPEED) SHOWN UNDER WIND DESIGN BASIS. |
| | 7D.) THERE ARE NO WINDOWS ON THE WEST SIDE OF HOUSE, AS |
| | INDICATED ON PAGE 3 OF THE SUMMARY CHECKLIST FORM |
| | R405-2020. THE CHECKLIST AND/OR PLAN SHEETS NEED TO BE |
| | CORRECTED. |
| | 7E.) THE BUILDER NEEDS TO COMPLETE AND SIGN THE EPL |
| | DISPLAY CARD. |
| | 8A.) SINGLE HUNG WINDOW NOA 17-1212.21 HAS EXPIRED. |
| | PROVIDE A CURRENT NOA. |
| | 8B.) THERMA TRU DOOR PRODUCT APPROVAL # FL 8871 WAS FOR |
| | THE LAST CODE CYCLE. PROVIDE CURRENT PRODUCT APPROVAL. |
| | ALSO INCLUDE THE COVER PAGE THAT CORRESPONDS TO THE |
| | SUBMITTED DRAWINGS. |
| | 9A.) THE AFFIDAVIT OF PRODUCT APPROVALS FROM PLAN SHEET |
| | A-1 DOES NOT MATCH THE SINGLE HUNG WINDOW NOA THAT WAS |
| | SUBMITTED. |
| | 9B.) THE AFFIDAVIT OF PRODUCT APPROVALS FROM PLAN SHEET |
| | A-1 DOES NOT MATCH THE DOOR PRODUCT APPROVAL THAT WAS |
| | SUBMITTED. |
| | 9C.) THE ROOF HIP AND RIDGE NOA ON PLAN SHEETS DOES NOT |
| | MATCH THE SUBMITTED NOA. |
| | |
| | |
| | |