2022-03-25 08:38:37PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS POOL IS LOCATED IN A SPECIAL FLOOD HAZARD AREA.
 THE POOL EQUIPMENT IS REQUIRED TO BE AT OR ABOVE THE
 ELEVATION OF THE FINSIH FLOOR OF THE HABITAL AREA OF
 THE DWELLING. FBC-R 322.1.6
  
 2) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE POOL GUARD SURFACE
 MOTION POOL ALARM AND SHOW THAT SHOW IT IS CERTIFIED TO
 ASTM STANDARD F2208. FBC-R 4501.17.1.9