| Plan Review Notes For Permit 22020102 |
| Permit Number |
22020102 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-22 14:24:50 | FIRE PROVISO: | | | | | | 1) THE SUPPRESSION SYSTME SHALL BE CONNECTED TO THE | | | EXISTING FIRE ALARM SYSTEM PER NFPA 96; | | | | | | 10.6 SYSTEM ANNUNCIATION. | | | | | | 10.6.1 UPON ACTIVATION OF AN AUTOMATIC | | | FIRE-EXTINGUISHING SYSTEM, | | | AN AUDIBLE ALARM OR VISUAL INDICATOR SHALL BE PROVIDED | | | TO | | | SHOW THAT THE SYSTEM HAS ACTIVATED. | | | | | | 10.6.2 WHERE A FIRE ALARM SIGNALING SYSTEM IS SERVING | | | THE OCCUPANCY | | | WHERE THE EXTINGUISHING SYSTEM IS LOCATED, THE | | | ACTIVATION | | | OF THE AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL | | | ACTIVATE | | | THE FIRE ALARM SIGNALING SYSTEM. | | | | | | PLEASE REVIEW AND ENSURE COMPLIANCE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|