Plan Review Notes
Plan Review Notes For Permit 22020102
Permit Number 22020102
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-02-22 14:24:50FIRE PROVISO:
  
 1) THE SUPPRESSION SYSTME SHALL BE CONNECTED TO THE
 EXISTING FIRE ALARM SYSTEM PER NFPA 96;
  
 10.6 SYSTEM ANNUNCIATION.
  
 10.6.1 UPON ACTIVATION OF AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM,
 AN AUDIBLE ALARM OR VISUAL INDICATOR SHALL BE PROVIDED
 TO
 SHOW THAT THE SYSTEM HAS ACTIVATED.
  
 10.6.2 WHERE A FIRE ALARM SIGNALING SYSTEM IS SERVING
 THE OCCUPANCY
 WHERE THE EXTINGUISHING SYSTEM IS LOCATED, THE
 ACTIVATION
 OF THE AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL
 ACTIVATE
 THE FIRE ALARM SIGNALING SYSTEM.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
  