| 2022-02-04 10:51:29 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE APPLICATION STATES "REMOVE AND REPLACE FLOOR" |
| | HOWEVER, THERE IS NO INDICATION OF THE PROPOSED |
| | REPLACEMENT FLOOR TYPE, NOR ITS MANUFACTURES SPEC |
| | SHEET. |
| | |
| | PLEASE PROVIDE THE FLOORING TYPE I.E. CERAMIC, MARBLE, |
| | TERRACOTTA, STONE OR OTHER TYPE OF TILE PRODUCT TYPE |
| | I.E. VINYL OR VINYL PLANKS, CORK, WOOD. |
| | |
| | FOR FLOORING PRODUCT TYPE OF VINYL OR VINYL PLANKS, |
| | CORK, WOOD, ETC, PLEASE PROVIDE THE MANUFACTURE PRODUCT |
| | FLAME SPREAD/PRODUCT SAFETY TEST SHEET |
| | |
| | VINYL FLOORING IS MANUFACTURED AROUND THE WORLD AND NOT |
| | ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. |
| | |
| | IF THE PROPOSED IS PORCELAIN OR CERAMIC TILE, NATURAL |
| | STONE TILE, CONCRETE TILES, SPEC SHEETS WOULD NOT BE |
| | REQUIRED. |
| | |
| | |
| | 2) THERE IS NO INDICATION OF FIRE SPRINKLER |
| | MODIFICATION WORK. |
| | |
| | WITH ANY REMOVAL OF WALLS, ENSURE CODE COMPLIANT |
| | SPRINKLER HEAD COVERAGE IS MAINTAINED. |
| | |
| | ANY REQUIRED FIRE SPRINKLER WORK SHALL BE DONE UNDER |
| | SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT |
| | DEMO AND CONSTRUCTION. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |