Plan Review Notes
Plan Review Notes For Permit 22020094
Permit Number 22020094
Review Stop B
Sequence Number 1
Notes
Date Text
2022-02-22 15:04:32WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22020094
 ADD: 3920 N FLAGLER DR.# 401
 CONT: MARYJULI CONSTRUCTION, INC.
 TEL: 561-386-6032
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 22/2022
 ACTION: DENIED
  
 1) PLEASE NOTE THE DOLLAR AMOUNT OF WORK TO BE COVERED
 UNDER THIS PERMIT IS $138,500.00 DOLLARS IN VALUE.
 PLEASE REVIEW FLORIDA STATUTE 481.229 EXCEPTIONS;
 EXEMPTIONS FROM LICENSURE (1)( C ).
  
 481.229 EXCEPTIONS; EXEMPTIONS FROM LICENSURE (1)(C)
 ANY OTHER TYPE OF BUILDING COSTING LESS THAN
 $25,000.00, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER
 BUILDING INTENDED FOR PUBLIC USE, PROVIDED THAT THE
 SERVICES OF A REGISTERED ARCHITECT SHALL NOT BE
 REQUIRED FOR MINOR SCHOOL PROJECTS PURSUANT TO 1013.45.
  
 2) SHEET A-2 IN THE NOTES THE FLOOR SOUND PROOFING TO
 BE INSTALLED IS CALLED OUT AS PROFLEX MSC-90. THIS
 REVIEW NO SUCH REPORT WAS SUBMITTED. TO DATE THE CITY
 HAS NOT RECEIVED A PROFLEX MSC 90 THAT HAS PASSED THE
 STC AND IIC RATING ON A 6-INCH CONCRETE SLAB, NO
 DROPPED CEILING!!!!! THE FINISH FLOOR HAS NOT BEEN
 IDENTIFIED IN THE PLANS.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 2C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253.
  
 3) SHEET A.2 DOES NOT MENTION THE TYPE OF BACKER BOARD
 FOR THE SHOWERS, NOR HEIGHT OF TILE.
 3A) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS
 A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 3B) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 4) SHEET A.2 SHOWS NEW SOFFITS IN THE KITCHEN AND
 BATHROOMS BUT THERE IS NO DETAILS SHOWING THE TYPE OF
 FRAMING MEMBERS, SIZE OF FRAMING MEMBERS AND SPACING.
 THERE IS NO MENTION OF WHERE THE SOFFIT FRAMING MEMBERS
 ARE TO BE ANCHORED, WALL OR DECK ABOVE OR BOTH NOR THE
 SPACING OF ANCHORS.
  
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL
 BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  