Notes
Date Text
2022-03-04 09:24:52ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE CLARITY ON THE FOLLOWING
 PLEASE PROVIDE CLARITY ON WHAT THE USE IS OF THE ROOM
 WHERE ELECTRIC PANEL IS LOCATED.
 THE ELECTRIC RISE STATES METER IS EXISTING. NOTES STATE
 ELECTRIC METER TO MOVE TO NEW LOCATION , HOWEVER THE
 DRAWING DOES NOT DATAIL THE NEW LOCATION, PLEASE
 PROVIDE CLARITY.
 PLEASE PROVIDE CLARITY AS TO WHETHER THE EXISTING BED
 ROOMS HAVE SMOKE ALARMS AS REQUIRED.
 PLEASE PROVIDE CLARITY AND SPECIFICATIONS ABOUT
 FAN/LIGHT COMBINATION IN ELECTRIC PANEL ROOM
 FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  