Plan Review Notes
Plan Review Notes For Permit 22020068
Permit Number 22020068
Review Stop P
Sequence Number 1
Notes
Date Text
2022-02-14 15:15:251ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22020068
 2/14/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) CS-1 & P1: REFER TO TABLE 403.1 FBC P AND PROVIDE
 PLUMBING FIXTURE CALCULATIONS FOR THE NEW RESTROOM
 BUILDING. PROVIDE A SCHEDULE INDICATING THE REQUIRED
 AND PROVIDED NUMBER OF FIXTURES. PLEASE NOTE THAT U
 OCCUPANCY CLASSIFICATIONS (SEE SEC. 312.1 FBC B) ARE
 NOT INCLUDED IN TABLE 403.1 FBC P. CLARIFY HOW THE
 NUMBER OF FIXTURES FOR THE RESTROOM WERE DETERMINED AND
 NOTE SERVICE SINKS FOR BUILDING SANITATION ARE REQUIRED
 FIXTURES FOR MOST USES AND OCCUPANCIES.
  
 2) A1: FBC- 2020 ACCESSIBILITY CODE CORRECTIONS-
 A) SHOW THE CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER
 CLOSETS- SEC. 604.3.
 B) SHOW THE CLEAR FLOOR SPACE DIMENSIONS FOR THE
 LAVATORIES- 606.2.
 C) SHOW THE TURNING SPACE DIAMETERS- 304.3.
 D) SHOW THE HEIGHTS OF THE MIRRORS FROM THE FINISHED
 FLOORS TO THE REFLECTIVE SURFACES- 603.3.
 E) SHOW THE MINIMUM LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- 604.5 & 609.4, AS
 DEPICTED IN FIGURES 604.5.1 & 604.5.2. THE CURRENT
 DETAILS DO NOT SHOW THE MINIMUM 54-INCH SIDE BAR
 EXTENSION FROM THE REAR WALL, AND THE MOUNTING HEIGHTS
 TO THE TOPS OF THE GRAB BAR GRIPPING SURFACES.
  
 3) A2: ROOF DRAINAGE: PLEASE SEE TABLES 1106.3 & 1106.6
 FBC P AND PROVIDE THE GPM CAPACITIES OF THE GUTTERS AND
 DOWNSPOUTS IN ORDER TO VERIFY SIZES ARE CODE COMPLIANT.
  
 4) REFER TO SECS. 403.3.3 & 403.5 FBC P AND VERIFY THE
 LOCATIONS OF THE RESTROOM FIXTURES AND DRINKING
 FOUNTAINS DO NOT EXCEED A TRAVEL DISTANCE OF 500 FT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  